Application manual
KNX binary output modules EK-GA1-TP
Release 1.5 - Update: 02/2022
MAEKGA1TP_EN
© EKINEX S.p.A. - All rights reserved
Page 34
6.5.3.3
Lock function
Parameter name
Conditions
Settings
Lock device signal
Locking function = enabled
not inverted
/ inverted
Allows to interpret a “lock activate” telegram as unlock and vice-versa.
After bus recovery
Locking function = enabled
unlock
lock
previous state
Defines how to set the lock status after bus voltage recovery.
Behaviour at locking
Locking function = enabled
off
on
no change
Defines how to set the output value when the lock is activated.
Behaviour at unlocking
Locking function = enabled
off
on
no change
updated value
value before locking
Defines how to set the output value when the lock is deactivated.
Updated value is the latest one that the output would assume if it had not been locked, i.e. it includes
the output value change generated by whatever other function in the meantime.
Value before locking is the value that the output had before the lock was activated.