
Application manual
KNX binary output modules EK-GA1-TP
Release 1.5 - Update: 02/2022
MAEKGA1TP_EN
© EKINEX S.p.A. - All rights reserved
Page 32
Object name
Conditions
Size
Flags
DPT
CO number(s)
Output
x
–
Forcing command
Forcing function =
enabled
2 bit
C-W--
[2.001]
switch control
9, 31
Allows to
force the status of an output (with respect to the “On/Off” status only)
It is composed of 2 bits: the first one is used for the priority value (i.e. defines whether the forcing
is in effect, “Priority”, or not) and the second one for the imposed value (which is not considered if
forcing is not effective).
Output
x
–
Logic object
n
Forcing function =
enabled
Logic object
n
= enabled
1 bit
CRWTU
[1.*]
generic 1-bit
Output 1
: 10...17
Output. 2
: 32...39
For each channel, it indicates the sequence of corresponding numbers for all 8 available logic
objects.
Output
x
–
Scene number
Scene function =
enabled
1 Byte
C-W--
[17.001]
scene number
[18.001]
scene control
18, 40
Allows to recall a scene setting for the status of the output, and to store current status (both
On/Off status and dimming value) in association to the specified scene.
Output
x
–
kWh counter
Operating hours / energy
counter = enabled
4-byte
signed
counter
CR-T-
[13.013]
active energy [kWh]
19, 41
Stores the current counter value of the accumulated energy.
Output
x
–
kWh counter
reset command
Operating hours / energy
counter = enabled
1 bit
C-W--
[1.015] reset
20, 42
Resets the energy counter to 0.
Output
x
–
Hours counter
Operating hours / energy
counter = enabled
2-byte
unsigned
counter
CR-T-
[7.007]
time [h]
21, 43
Stores the current counter value of the accumulated operating time.
Output
x
–
Hours counter
reset command
Operating hours / energy
counter = enabled
1 bit
C-W--
[1.015] reset
22, 44
Resets the operating hour counter to 0.