3) When the required operation is finished, manual mode is turned off by pressing the mode pushbutton
again. Upon returning to bus-controlled mode, the output values will be restored as already
described.
Switching to manual mode through the front panel can be inhibited in two ways, both selectable through
configuration parameters:
by disabling the manual switching feature altogether;
through a bus command.
Please notice that the above-mentioned bus command inhibits switching to manual through the panel key; it
does not switch modes itself.
If manual mode is neither inhibited by configuration nor controllable through the bus, another parameter
allows setting a timeout period after which, whenever the device is left in manual mode, it will be reverted to
bus-controlled mode. This prevents the device to be inadvertently left in an unintended state.