28
8.1 General
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to:
USA- National Electrical Code, ANSI/NFPA 70.
•
Canada - Canadian Electrical Code, Part I, CSA C22.1:
•
Safety Standard for Electrical Installations.
8.2 Line Voltage Connections (Figure 8-1)
Boiler
•
Provide individual 120V, 15 amp circuit (recom-
A.
mended) with fused disconnect or service switch,
as required by authority having jurisdiction.
Open High Voltage Junction Box (see Figures 3-1,
B.
3-2) to access line voltage terminal strip.
Connect 120 VAC circuit to line voltage terminal
C.
strip 120 VAC L,N,G.
Central Heating Pump, if used.
•
Isolate pump from control module if pump FLA (Full
A.
Load Amps) exceeds 5 amps.
Connect pump to line voltage terminal strip CH
B.
PUMP L,N,G.
Domestic Hot Water Pump, if used.
•
Isolate pump from control module if pump FLA
A.
exceeds 1.0 amp.
Connect pump to line voltage terminal strip DHW
B.
PUMP L,N,G.
8.3 Low Voltage Connections
(Figure 8-2)
User Interface Terminals
•
Factory wired to low voltage terminal plug USER
A.
INTERFACE terminals
Optional - Remote mount user interface for
B.
improved access.
Maximum wire length is 100 ft (30m) for 22 ga.
C.
wire, or 150 ft (45m) for 18 ga. wire.
Argus Link (Multiple boiler applications only)
•
Outdoor Sensor, if used.
•
Provided with boiler in accessory kit.
A.
Locate outdoor sensor to protect against wind and
B.
direct sunlight. Mounting instructions provided with
sensor.
Maximum wire length is 100 ft (30m) for 22 ga.
C.
wire, or 150 ft (45m) for 18 ga. wire.
Connect wires to low voltage terminal plug OUT-
D.
DOOR SENSOR terminals. Wires are interchangeable.
System Sensor (Multiple boiler applications only)
•
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
!
8 - ELECTRICAL CONNECTIONS
8-1 LINE VOLTAGE CONNECTIONS
8-2 LOW VOLTAGE CONNECTIONS
NOTICE
Wiring diagrams can be found in Section 14 of this
Manual
.