65
User Interface Display
Explanation
Installer Menu
Installer Menu
I N S T A L L E R M E N U
B o i l e r
S t a t u s
B o i l e r
C o n f i g
C H
S e t t i n g s
D H W
S e t t i n g s
C a s c a d e
S e t t i n g s
S y s t e m T e s t
The Installer Menu structure includes:
‘Boiler Status’ submenu – User monitors detailed boiler
•
status parameters such as fl ame signal, fan speeds and
stored error codes.
‘Boiler Confi g’ submenu – Modifi es general boiler
•
settings.
‘CH Settings’ submenu – Modifi es advanced Central
•
Heating settings including outdoor reset curve
parameters and boost function.
‘DHW Settings’ – Modifi es Domestic hot Water control
•
settings such as DHW priority time.
‘Cascade Settings’ - Refer to Multiple Boiler Manual.
•
‘System Test’ – Tool aids setup of boiler installation or
•
diagnosis of common problems.
Boiler Status
S T A T U S
F a n S p e e d
A c t u a l
4 0 0 0 R P M
L o w
P o w e r
1 5 6 0 R P M
▼
Combustion air Blower provides airfl ow through Combustion and
Vent systems.
Fan speed status screen indicates actual and operational fan
speeds in RPM, high, low and ignition power speed settings.
Settings are for information only to aid in troubleshooting.
S T A T U S
▲
F a n S p e e d
I g n i
t
i o n
3 5 0 0 R P M
H i
P o w e r
5 7 2 5 R P M
▼
S T A T U S
▲
F l a m e
S i g n a l
0 7 . 2 u A
F a i
l u r e s
2
▼
Boiler equipped with ionization rod to detect presence of
combustion using fl ame rectifi cation method. When fl ame is
present, fl ame ionization rod measures small DC offset current
across fl ame to ground (i.e. burner surface).
‘Flame’ screen in ‘Boiler Status’ submenu displays information
regarding fl ame ionization system; for information only and
used in diagnosing combustion problems. See troubleshooting
guide.
APPENDIX A - CONTROL MODULE
Summary of Contents for 075 97gb
Page 56: ...56 14 WIRING DIAGRAM 14 1 Connection Diagram ...
Page 57: ...57 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form ...
Page 73: ...73 ...
Page 74: ...74 ...
Page 75: ...75 ...