ecoSMART Supervisor user, installer and technical service manual
29
EN
6.
Configuration and commissioning
NOTE
Before starting control configuration, ensure that the pLAN connection terminals are disconnected.
Leaving the pLAN cable connected may cause the supervisor components or the components it
controls to malfunction or even break down.
If the software needs t
o be updated or the configuration needs to be deleted (installer menu →
default values) keep the pLAN cable disconnected.
Follow the configuration steps in the order shown in this section. Any change in the configuration
order may cause the unit to malfunction. If the configuration order is changed, delete the
configuration using the tool found in "installer menu → default values" and start again.
6.1.
Software version and "default values"
Make sure the supervisor has the same software version number as the heat pumps.
The software version can be found in “user
menu
→
information” and in “installer menu →
information”. The software version number is identified by the code Vxx_Bxxx (e.g.
figure 6.1).
If necessary, update the supervisor software or even the software of all the devices on the pLAN network. Make sure to install the
correct software for each device. As shown in figure 6.1, the ecoGEO HP heat pump software is identified by the letters "HP" and
the supervisor software by the letters "PS".
ecoGEO HP
Supervisor
Figure 6.1.
Example information screens showing the ecoGEO HP heat pump and ecoSMART Supervisor software version.
Check that there is no configuration in the supervisor electronic control. If there are any configuration parameters or if you are not
sure, delete
the whole configuration using the tool in “installer menu → default values”.
6.2.
pLAN address configuration in heat pumps
To configure pLAN address access IN EACH HEAT PUMP, WHICH WILL BE MANAGED BY SUPERVISOR, TO THE INSTALLER MENU
(press [Prg]+[Esc] and enter the installer password PW1) -> CONFIGURATION ->REMOTE CONTROL ->CASCADE MODE.
1.
On the pLAN MASTER/SLAVE ENABLED / DISABLED cascade mode.
2.
Select the unit control address. Address 15 is reserved for supervisor, select between 1 and 6 for each heat pump, select a
logical order. Do not repeat address in heat pumps. Please see the sample below in the Figure 6.2.
Address 1
Address 2
Address 3
Address 4
Address 5
Address 6
Figure 6.2.
Cascade with ecoGEO HP heat pumps with the address related to each heat pump number.