background image

ecoSMART Supervisor user, installer and technical service manual 

 

 

 

16 

 

EN

 

Figure 4.8.

 Example of digital output relay power supply connections. 

Each relay allows independent pole switching; it can thus control the switching on/off of the units, including those powered with a 
different  voltage.  The  capacity  of  the  relays  is  8A/250Vac  per  pole.  If  the  equipment  to  be  controlled  exceeds  this  capacity,  an 
external  relay  or  contactor  must  be  installed.  Shown  below  are  examples  of  connections  between  circulator  pumps  and  3-way 
valves with controls at 2 or 3 points. 

 

 

NOTE 

 

Pay  special  attention  to  the  maximum  consumption  allowed  by  each  relay.  Use  an  intermediate 
relay or a contactor for the connection, if necessary.

 

 

 

Figure 4.9.

 Example of digital output connections. 

 

Description 

Signal 

Type 

Connector 

Brine pump activation 

Digital output 

Activation 230Vac / 8A maximum 

DO1 

Production pump / buffer pump activation 

Digital output 

Activation 230Vac / 8A maximum 

DO2 

Auxiliary brine pump activation 

Digital output 

Activation 230Vac / 8A maximum 

DO3 

Auxiliary pump cool tank activation 

Digital output 

Activation 230Vac / 8A maximum 

DO4 

Free cooling production activation 

Digital output 

Activation 230Vac / 8A maximum 

DO5 

Auxiliary heating system activation 

Digital output 

Activation 230Vac / 8A maximum 

DO6 

Active cooling production activation 

Digital output 

Activation 230Vac / 8A maximum 

DO7 

DHW production activation 

Digital output 

Activation 230Vac / 8A maximum 

DO8 

Free 

Digital output 

Activation 230Vac / 8A maximum 

DO9 

Free 

Digital output 

Activation 230Vac / 8A maximum 

DO10 

 

Table 4.4.

 List of the connections of external equipment to the upper terminal blocks of relays. 

 

 

4.2.

 

Power supply 

The  supervisor  only  requires  one  electrical  connection.  The  power  supply  to  the  24Vac  transformer  connects  to  it  to  power  the 
controller and other devices with low power consumption. The following table shows the characteristics of the necessary electrical 
connection: 

Type of power supply 

Type of protection/ Cut-off current 

Recommended cable section 

1/N/PE 230 V / 50-60 Hz 

Magnetic, thermal and differential / 1A 

1.5 mm

2

 

 

DI7 DI8

DI5

DI4

DI3

DI2

DI1

AI12

AI11

AI10

AI9

DI6

AO5

AO4

AO3

AO2

AO1

AI8

AI7

AI6

AI5

AI4

AI2

AI1

AI3

Sgn

C

o

m

Sgn

24

V

a

c

Sgn

24

V

a

c

Sgn

24

V

a

c

Sgn

24

V

a

c

Vou

t

24

V

a

c

G

N

D

PE

G

N

D

Tx

/R

x+

Tx

/R

x-

Sgn

C

o

m

Sgn

C

o

m

Sgn

C

o

m

Vou

t

24

V

a

c

G

N

D

Vou

t

24

V

a

c

G

N

D

Vou

t

24

V

a

c

G

N

D

Vou

t

24

V

a

c

G

N

D

Sgn

Sgn

Sgn

Sgn

Sgn

Sgn

Sgn

G

N

D

G

N

D

G

N

D

G

N

D

G

N

D

G

N

D

G

N

D

Sgn

G

N

D

Sgn

G

N

D

Sgn

G

N

D

Sgn

G

N

D

Sgn

G

N

D

PE

G

N

D

Tx

/R

x+

Tx

/R

x-

PE

G

N

D

Tx

/R

x-

Tx

/R

x+

pLAN

BMS2

FBus

Fu

se

 2

A

24 Vac

Control Power

Supply 230V

DO1

DO2

DO3

DO4

DO5

DO6

DO7

DO8

DO9

DO10

DO11

DO12

DO13

L1 L2/N PE

Fu

se

 0

.5

A

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

L

off

L

on

L

NC: 22/12

COM: 21/11

NO: 24/14

A2/A1

 

DOxx

NC

COM

NO

NC: 22/12

COM: 21/11

NO: 24/14

A2/A1

 

DOxx

NC

COM

NO

2P

3P

Summary of Contents for ecoSMART Supervisor

Page 1: ...06 2020 SERVICE CONTACT MODEL ecoSMART Supervisor USER INSTALLER AND TECHNICAL SERVICE MANUAL EN...

Page 2: ......

Page 3: ...20 5 5 Operation program 21 5 6 Heatpump status 22 5 7 User menu 23 5 8 Installer menu 26 6 Configuration and commissioning 29 6 1 Software version and default values 29 6 2 pLAN address configuratio...

Page 4: ...ecoSMART Supervisor user installer and technical service manual 4 EN 10 Warranty and technical service 38 10 1 Manufacturer s warranty 38 10 2 Authorised distributors and technical service 38...

Page 5: ...acturer is not responsible for any material damage and or personal injury resulting from improper use or incorrect installation of the equipment The device must be installed by a licensed installer in...

Page 6: ...by an authorised electrician in accordance with applicable local regulations and the instructions provided in this manual DANGER The power supply to the unit must have an external switch that can shu...

Page 7: ...njury and or damage to materials Do not spill water or other liquids directly on the casing or inside it as this could cause an electric shock or fire 2 General description The ecoSMART Supervisor is...

Page 8: ...rench is required to assemble and disassemble the cover Remove the front cover by loosening the four screws and pulling it Figure 3 2 Removing the front cover of the supervisor 3 5 Location and assemb...

Page 9: ...upply to the unit must have an external switch that can shut off all the circuits Ecoforest recommends installing an automatic external switch for each of the electrical power sources power supply of...

Page 10: ...and pLAN Transformer fuse 230Vac 0 5A Main switch 24Vac transformer Digital outputs DOxx Control fuse 24Vac 2 5A DIxx Digital inputs Controller pCO OEM Main supply 1 N PE 230Vac 50 60 Hz DI7 DI8 DI5...

Page 11: ...3 DO8 S DI1 DI2 EVU DO2 2 DO1 2 DI1 DI2 EVU DO2 1 DO1 1 3 2 1 T T AI2 S AI1 S T T AI4 S AI3 S AO3 S DO6 S DO1 S AO1 S DO2 S AO2 S DO5 S M T T T T T T T T T DG1 SG3 SG4 SG2 T T T M M M T T FBus2 SG5 T...

Page 12: ...DO4 S M M T T DO5 S DO2 S AO2 S AO1 S DO8 S DI1 DI2 EVU DI1 DI2 EVU AI18 1 2 3 AI11 1 2 3 DO17 1 2 3 DO4 1 2 3 AI12 1 2 3 DO5 1 2 3 AI17 1 2 3 DO18 1 2 3 DI4 1 2 3 AI19 1 2 3 DO6 1 2 3 DO7 1 2 3 DO8...

Page 13: ...AI3 Production inlet temperature probe Analogue input NTC 10K 25 C Probe AI4 Outside temperature probe Analogue input NTC 10K 25 C Probe AI5 Free Analogue input NTC 10K 25 C Probe AI6 Free Analogue i...

Page 14: ...nnection terminals of the external control signals 24Vac Sgn DIxx DI7 DI8 DI5 DI4 DI3 DI2 DI1 AI12 AI11 AI10 AI9 DI6 AO5 AO4 AO3 AO2 AO1 AI8 AI7 AI6 AI5 AI4 AI2 AI1 AI3 Sgn Com Sgn 24Vac Sgn 24Vac Sgn...

Page 15: ...ing figure shows an example of an installation of a relay power supply DI7 DI8 DI5 DI4 DI3 DI2 DI1 AI12 AI11 AI10 AI9 DI6 AO5 AO4 AO3 AO2 AO1 AI8 AI7 AI6 AI5 AI4 AI2 AI1 AI3 Sgn Com Sgn 24Vac Sgn 24Va...

Page 16: ...Activation 230Vac 8A maximum DO7 DHW production activation Digital output Activation 230Vac 8A maximum DO8 Free Digital output Activation 230Vac 8A maximum DO9 Free Digital output Activation 230Vac 8...

Page 17: ...ation included below corresponds to application versions launched after October 2019 Other versions both earlier and later may differ slightly from the contents found in this section Depending on the...

Page 18: ...accessed directly from anywhere in the application The list of user menus can be accessed from anywhere in the application The user can return to the previous menu from anywhere in the application Thi...

Page 19: ...tive components This field shows the main components of the heat pump that are activated A consumption bar is also shown for the compressor and modulating circulator pumps Brinepumpactivated Compresso...

Page 20: ...is lower higher than the differential of start up temperatures DHW mode The heat pump sends hot water to increase the temperature of the storage tank so it reaches the DHW setpoint temperature as soo...

Page 21: ...The minutes remaining for the compressor to start up are shown next to the icon STAND BY No demand The heat pump remains in standby because there is no demand 5 5 Operation program The heat pump oper...

Page 22: ...s functions OFF status due to supervisor In facilities with several units operating in parallel the heat pump is switched off by the supervisor and is therefore not available to activate any of its fu...

Page 23: ...llows the heat pump to be switched between ON OFF REMOTE The selected state can be modified via the programming of the schedule or alarm Also allows the operating program to be selected between WINTER...

Page 24: ...times when time changes occur MENU 1 2 1 Holidays Allows three holiday periods to be defined during which the supervisor RESPONDS DOES NOT RESPOND to the services requested The settings on this screen...

Page 25: ...e enabled the current state of each one On Off and the heat pumps stopped or locked by alarm HP AVAILABILITY This screen shows the operating hours accumulated in each heat pump Also with an upward arr...

Page 26: ...ine alarm Cold outlet alarm 2 2 5 Probe configuration Brine outlet temp Brine inlet temp Heating outlet temp Heating inlet temp Outside temperature 2 3 Manual test Brine pump Production pump Auxiliary...

Page 27: ...mote control function to manage the ACTIVATION DEACTIVATION and the setpoints of each shunt groups in heating and cooling and the services DHW and POOL Also it allows to control the BUS remote control...

Page 28: ...the manual ENABLING DISABLING of the brine pump s control relay DO1 and for adjustments to be made to the rotational speed percentage PRODUCTION PUMP BUFFER PUMP Allows the relay to be manually ENABL...

Page 29: ...e or even the software of all the devices on the pLAN network Make sure to install the correct software for each device As shown in figure 6 1 the ecoGEO HP heat pump software is identified by the let...

Page 30: ...no 4 4 29 Heat pump no 5 5 28 Heat pump no 6 6 27 ecoSMART Supervisor 15 18 Table 6 1 Control addresses and control panel addresses for units connected via the pLAN network To configure these addresse...

Page 31: ...ged by supervisor 6 6 Service configuration To configure all the services configure it in each heat pump connected to supervisor the services HEATING COOLING DHW and or POOL that you want enabled The...

Page 32: ...check that all the circuits are flowing and that nothing is preventing the flow Check the following points to ensure that they have been carried out successfully Inspection of the electrical installa...

Page 33: ...tem starts to function normally and the button flashes to indicate that there has been an alarm This process may be repeated indefinitely the supervisor does not cause permanent locking Table 7 1 ther...

Page 34: ...Y4 DI9 DI10 DI9C J7 DI3 DI2 DI4 GND DI1 Tx Rx Tx Rx GNG J29 GND Tx Rx Tx Rx J10 FBUS1 J15 R9 R10 R11 R12 R13 DO9 DO10 DO11 DO12 DO13 GND Tx Rx Tx Rx J11 BMS2 GND Tx Rx Tx Rx J14 pLAN POWER SUPPLY Sgn...

Page 35: ...tion 250Vac 8A max Free Block I DO13 pCOOEM J28 NO13 Activation 250Vac 8A max Free COMMUNICATIONS CONNECTIONS DESCRIPTION Connection terminal Controller terminal Type Signal Block II FBus1 pCOOEM J9 F...

Page 36: ...heating system regulation Block II AO4 pCOOEM J26 Y4 0 10Vdc Free Block II AO5 pCOOEM J26 Y5 0 10Vdc Free DIGITAL INPUTS CONNECTIONS DESCRIPTION Connection terminal Controller terminal Type Signal Blo...

Page 37: ...valve 0 10Vdc Cooling system Check valve NTC temperature probe Cut off valve Relay thermostat Safety valve Data bus communication terminal Differential pressure valve Circulator pump Particulate filt...

Page 38: ...aser must inform the establishment that sold the product of the lack of conformity within 30 thirty days For the warranty to be effective the purchaser must present a legal document that supports the...

Page 39: ......

Page 40: ...mpresarial Porto do Molle R a das Pontes 25 36350 Nigr n Pontevedra Spain Tel 34 986 262 184 http www ecoforest es The manufacturer reserves the right to make any necessary changes to the contents of...

Reviews: