16
www.ecoflamburners.com
EN
420010372500
Service
Maintenance
Burner and boiler servicing must only
be carried out by qualified personell.
The system operator is advised to take
out a service contract to guarantee
regular servicing.
Attention
• Disconnect the electrical supply before
carrying out any maintenance or
cleaning work.
• The blast tube and firing head may be
hot.
Checking the exhaust gas temperature
• Check the flue gas temperature at
regular intervals.
• Clean the boiler if the flue gas
temperature is more than 30°C above
the value measured at the time of
commissioning.
• To simplify the check, use a flue gas
temperature indicator.
Maintenance on the burner
• Check oil supply components (tubes,
lines) and their connections for leaks or
signs of wear, replace if necessary.
• Check electrical connections and
connection cables for damage, replace if
necessary.
• Check oil filter, clean or replace as
necessary.
• Clean fan wheel and housing and check
for damage.
• Check and clean the mixing unit.
• Check ignition electrodes block, readjust
or replace as necessary.
• Start burner, check flue gas data, correct
burner settings if necessary.
• Check the setting for air pressure switch.
• Carry out an operating check.
• Check the oil filter.
Recording commissioning data
Test
n°1
n°2
Date
Model
Type oil
Oil calorific value
Burner output
min kW
Burner output
max kW
Flue gas temperature
C°
Air temperature
C°
CO
2
%
CO
ppm
NOx
ppm
Performance
%
Corrective action
Operator name
Company
WARNING
Summary of Contents for 3121067
Page 65: ...65 www ecoflam burners com 420010372500 RU 5 60 6 A 50 100 mm A1 50 100 mm A A1 4 3...
Page 68: ...68 www ecoflam burners com 420010372500 RU 30 C n 1 n 2 min max C C CO2 CO ppm NOx ppm WARNING...
Page 69: ...69 www ecoflam burners com 420010372500 RU I 1 2 3 10 AL LED 10 2 TSA 3 4 5 6 7 8 5 9 10 off 3...
Page 70: ...70 www ecoflam burners com 420010372500 RU 0 2 2 2 2...