IAQH-1000 Manual
227
PWM blower
parameterization error
One or more PWM blower settings are not compatible.
Make sure the following three conditions on the
minimum and maximum speed settings are met.
1. 516.00 ≤ P0 ≤ 516.01
2. 517.00 ≤ P1 ≤ 517.01
3. 518.00 ≤ P2 ≤ 518.01
rSt Er1
Incompatible PME7 and
LME7
The PME7 program module and LME7 base unit being
used are incompatible. PME71 program modules are
only compatible with LME71 base units, PME73
program modules are only compatible with LME73 base
units, and PME75 program modules are only compatible
with LME75 base units.
rSt Er2
rSt Er3 Fault during restore process The PME7 program module was removed during the
restore process. Re-install the PME7 program module
and reset the fault to complete the restore process.
bAC Er3 Fault during backup process The PME7 program module was removed during the
backup process. Re-install the PME7 program module
and reset the fault. Perform the backup process again.
Err PrC No program module
detected
This fault occurs when no PME7 program module is
plugged into the LME7 base unit. Insert a PME7
program module into the LME7 base unit and reset the
fault.