Layout Plan
Indoor Mounted System:
This unit is designed to be mounted internally into the structure it is heating, following all
clearance distances found in Section 4.2.2.
Ensure the unit is only installed onto a
non-combustible floor.
Horizontal Venting:
Venting must be done in accordance with CSA B149.1 or NFPA 54 or with appropriate local
authorities having jurisdiction.
1. The flue must be securely attached to the unit with tight joints
2. Other appliances must not be connected so as to use the same venting
3. Do not use 90-degree tees or elbows greater than 45-degrees.
4. Do not support the weight of the stack on the flue connection of the heating system, the
heat exchanger is not designed to support this additional weight in excess of five vertical
feet
5. The maximum flue gas temperature is 650 °F (345 °C). “A” vent, or single wall steel pipe
must be used
6. Minimize connecting pipe length and the number of bends by locating the unit as close
to the flue pipe as possible
7. Maintain clearances between the flue pipe and combustible materials that are
acceptable to the Federal, Provincial and local authorities having jurisdiction. Unit must
be connected to a flue having sufficient draft to ensure proper operation of the unit
Vent installations shall conform with local codes, or, in the absence of local codes, with the
National Gas and Propane installation Code CSA B149.1 or National Fuel Gas Code, ANSI
Z223.1/NFPA 54 (see Fig. 5).