IAQH-1000 Manual
The exhaust venting chimney must maintain the following clearances from the building area or
structure.
Structure / Object
Minimum Clearance
Air Intake
0.9m (3’) above and 1.8m (6’) to the side
Combustion air intake from another heater
1.8m (6’) above and 1.8m (6’) to the side
Door, openable window, revolving door
or all other openings
1.8m (6’) to the side
0.9m (3’) above
Electrical or gas meter, regulator and
relief
1.8m (6’) to the side (Canadian standards)
1.2m (4’) to the side (U.S.A. standards)
Vent outlet from another service
0.9m (3’)
Building or adjacent wall
1.8m (6’) (might have to be increased for
horizontal
Sidewalk or parking lot
2.1m (7’) above
Ground vent
0.3m (1’) above snow level
Wall of vent outlet
0.3m (1’) minimum
Roof of vent outlet
0.9m (3’) minimum and 0.6m (2’) above all
obstacles within less than 3m (10’)
44