Resetting Faults on the LME7 Burner Control
Faults can be reset in one of three ways on the LME7
…
burner control:
1. Pressing the info button on the LME7 burner control for 1-3 seconds.
Note: Pressing the info button for less than one second has no effect. Pressing the info button
for more than three seconds places the LME7 into diagnostic mode.
2. Pressing the info button on the AZL23 remote display until the word “rESET” appears, then
releasing.
Note: Releasing the info button before the word “rESET” appears has no effect.
Pressing the info button too long accesses the “InFo” menu.
3. Pushing the burner reset button the main control panel of the unit, note pushing this for less
than one second has no effect.
Accessing the Service (SEr) Menu
The service (SEr) menu contains the fault history as well as the 900 series of parameters that
are used for diagnostic purposes, such as flame signal (954) and incoming voltage (951).
1. From the home screen (OFF), press and hold the info button until the word “SEr” is displayed,
then release the button. The word “InFo” will briefly be displayed before “SEr”.
2. Press the + or - button to navigate through the parameters in the “SEr” menu.
3. When finished, press the “+” and “-” buttons together to escape.