IAQH-1000 Manual
7. Ensure that the burner intake vents are not blocked and that debris or snow will not
enter the enclosure during normal operation.
8. Do not place the unit in close proximity to alternate heat sources. Maintain 6 feet
(2 meters) of clearance.
9. Position the unit so that power and gas connections are not in hazardous or high traffic
areas.
10. Electrical
a. This appliance is designed to receive 208 V three phase power with a frequency
of 60 hertz — it is important that the supply voltage remains constant and that
low and high voltage conditions are avoided.
b. Size your wire in line with the amperage rating of the circuit, taking into account
derating for distances, see cable manufacturer rating for information or refer to
CSA C22.1 for additional information as a general reference:
i.
10 AWG to 50’
ii.
6 AWG to 100’
iii.
4 AWG to 200’
c. The electrical grounding of the appliance shall be in compliance with the
National Electrical Code, NFPA 70, or CSA C22.1, Canadian Electrical Code, Part I.
11. Gas Connections
a. Ensure gas connections are in compliance with the local authority having
jurisdiction , or in the absence of local codes CSA B149 or NFPA 54.
b. Inlet gas train pressure must not exceed 14” W.C — sizing the gas regulation
equipment for this equipment is critical to safe and reliable operation.
c. Sizing of gas supply lines and proper sizing are critical, refer to CSA 149.1 for
proper line sizing based on your pressure.
d. After installation, check the manifold gas assembly for gas leaks by applying a
water and soap solution to each connection and observing for bubbles, note in
colder weather it is recommended to use a cold weather rated solution
46