4. Using peripheral devices - External connections
4. Using peripheral devices - External connections
With its ports, Eaton's HMI makes it possible to connect a variety of peripheral
devices and components.
DANGER
STRAY CURRENTS
Large equalizing currents between the functional earthing system
and the ground system of different devices may result in fire or in mal-
functions due to signal interference.
If necessary, route an equipotential bonding conductor, with a
cross-sectional area that is several times larger than that of the
cable shielding, parallel to the cable.
CAUTION
INTERFERENCES
The values specified in the technical data, as well as the device's
electromagnetic compatibility (EMC), cannot be guaranteed if the fol-
lowing are used: unsuitable cables, improperly assembled and ter-
minated cables, and/or wiring that does not conform to the applicable
standards.
Only use cables assembled and terminated by professionals.
The cables being used must be assembled and terminated as
required by the port/interface description in this document.
When wiring the XP-504, follow all instructions regarding how to wire
the corresponding port/interface.
All general Directives and standards must be complied with.
49
XP-504
08/2021 MN048028EN Eaton.com
Summary of Contents for XP-504
Page 1: ...Manual 08 2021 MN048028EN XP 504 manual...
Page 4: ......
Page 14: ...0 1 About this documentation 15 XP 504 08 2021 MN048028EN Eaton com...
Page 62: ...5 Commissioning 5 2 Running the XP 504 63 XP 504 08 2021 MN048028EN Eaton com...
Page 66: ...6 Operation 6 2 Handling terminal 67 XP 504 08 2021 MN048028EN Eaton com...
Page 74: ...7 Operating system 7 2 Windows 10 Enterprise LTSC 75 XP 504 08 2021 MN048028EN Eaton com...
Page 76: ...8 Faults 77 XP 504 08 2021 MN048028EN Eaton com...
Page 94: ...Appendix A 2 Further usage information 95 XP 504 08 2021 MN048028EN Eaton com...