3. Installation
3.4 Mounting
3.4 Mounting
CAUTION
Arrange for a professional technician to mount the device.
CAUTION
INSTALLATION CUT-OUT
The mounting cutout must be located in a position that will not defeat
the purpose of stabilizing webs or other reinforcing elements in the
control panel. If necessary, reinforcing elements must be installed/ad-
ded.
An IP65 degree of protection will only be ensured if there is sufficient
stiffness and the device is properly mounted.
l
Minimum sheet thickness of control cabinet where the device will
be flush mounted:
1.5 mm (0.06“) ≦ d ≦ 4 mm (0.16“)
l
In order for the device to be properly mounted, every single one of
the holding brackets must be used at its intended spot.
List of tools:
l
Wrench for Allen key: 2 mm (5/64")
l
PZ2 Pozidriv screwdriver
l
Open-ended wrench SW10
l
ground straps: Length ≤ 35 cm, width ≥ 20 cm with eyelet
l
Torque wrench with Newton meter scale
XP-504
08/2021 MN048028EN Eaton.com
38