6
Installation
InstructIon manual
MN050011EN August 2022 www.eaton.com
Connecting the power supply
DANGER
IN SAFETY-RELEVANT APPLICATIONS, THE POWER SUPPLY
USED TO POWER THE XN300 SYSTEM MUST BE A PELV POWER
SUPPLY UNIT.
The two 24 V V+ terminals are internally connected to
each other (X6:
), as are the two 0 V GND terminals
). Only one V+ and one 0 V terminal need to
be connected in order to power the gateway. The internally
connected terminals can be used to extend the 24 V and
0 V supply voltage connections. However, it is necessary
to make sure that a total current of 4 A is not exceeded
per terminal.
External 24 Vdc voltages can also be distributed
using an XN-322-4PS-20 power distribution module or
XN-322-18PD-P and XN-322-18PD-M field potential
distributor modules.
The plug connector with push-in spring-cage terminal
FMC 1.5/4-ST-3.5 is included in the scope of supply.
Figure 11 . Connection of power supply
a
24 V V+
b
24 V V+
c
0 V GND
d
0 V GND
The device must be powered with a galvanically isolated
power supply with a rated voltage of 24 Vdc. A UL
T
249
fuse (maximum 4 A) must be installed between the power
supply and the device.
Figure 12 . Wiring the power supply
0.12 inch (3.0 mm)
F1
X6
U
e
= 24 Vdc
(18–30 Vdc SELV)
I
e
≤
0.2 A
V+
V+
0 V
0 V
0 V
24 Vdc
F1
F1
≤
4 A