Xiria
994.570 G01 06
17
Table 4: Short-circuit capacity in relation to cable cones used
Cone type
EN 50181
I [A]
Maximum
short-circuit current
Plug type
Cable type
Load-break
switch
C
630
3.6-24kV 20kA-3s
bolted T-plug
M16
Cu/Al XLPE
Cu/Al XLPE
Circuit-
breaker
A
200
3.6-24kV 20kA-0,4s
plug type
L plug
Cu/Al XLPE
Cu/Al XLPE
Circuit-
breaker
C
500 and
630
3.6-24kV 20kA-3s
bolted T-plug
M16
Cu/Al XLPE
Cu/Al XLPE
3.3.2
Cable assembly instructions
Strain relief
Strain relief prevents mechanical forces from being
transmitted to other parts of the unit via the cable
connection point.
Each panel is provided with three single phase plastic
cable clamps or one three phase plastic cable clamp
(Figure 3-7).
Assembly (standard)
WARNING
At delivery each cable cone type C is provided
wit
h a “temporarily” mounted allen key transport
bolt M16 x 30.
These bolts must be removed before connecting
the cable.
Figure 3-7: Cables with plastic cable clamps
Plinths can be removed for each panel when fitting the
cables if so desired.
Connect the cables to ensure that no mechanical forces
are created at the cable connection point.
The maximum torque for a C-type cone is 70 Nm.
The weight of the cable and tensile forces originating
from the cable must be absorbed by the cable clamp
blocks on the cable support.
Secure all cables using cable clamp blocks. This is in
order to enable the short-circuit forces to be absorbed in
the event of any short-circuit occurring.
Seal all cable recesses in the floor properly. Use
polyurethane with a compact cellular structure, for
instance. This will protect the cable connection
compartment from rising damp and vermin.
The cable clamp blocks are mounted on an adjustable
frame in the cable connection compartment. The bolts
through the plastic cable clamps must be tightened to a
torque of 20 Nm.
Summary of Contents for Xiria
Page 39: ...Xiria 994 570 G01 06 39 APPENDIX 1 FLOOR PLANS ...
Page 40: ...Xiria 40 994 570 G01 06 ...
Page 41: ...Xiria 994 570 G01 06 41 ...
Page 42: ...Xiria 42 994 570 G01 06 ...
Page 43: ...Xiria 994 570 G01 06 43 ...
Page 44: ...Xiria 44 994 570 G01 06 ...
Page 45: ...Xiria 994 570 G01 06 45 APPENDIX 2 VOLTAGE DETECTING SYSTEM WEGA ...
Page 46: ...Xiria 46 994 570 G01 06 ...
Page 47: ...Xiria 994 570 G01 06 47 ...
Page 48: ...Xiria 48 994 570 G01 06 APPENDIX 3 ORION 3 0 ...
Page 49: ...Xiria 994 570 G01 06 49 APPENDIX 4 SHORT CIRCUIT INDICATOR ...
Page 55: ...Xiria 994 570 G01 06 55 ...
Page 56: ...Xiria 56 994 570 G01 06 ...