Xiria
24
994.570 G01 06
4.2.2
Switch cable earthing on/off
In the operating position, the cable is connected to the
main busbar of the unit; the switch is ON and the change-
over switch is in the busbar position.
Initial position:
In the neutral position (see Figure 4-5):
the switch is OFF, see switch (4) position indicator;
the change-over switch is in earthed position, see
position indicator of change-over switch (9);
selector (7) is in the central position.
Figure 4-5: Panel in neutral position
Figure 4-6: Panel in earthed position
Procedure for switching cable earthing on
1.
Check the position indication to verify that the change-
over switch is in the earthed position. An additional
option is available to inspect the position of the
change-over switch through windows (14) at the front ,
see Figure 4-5. Check the position of all three phases:
use a torch to provide additional light through an
adjacent window;
check the position of the change-over switch;
Figure 4-7 shows the change-over switch in the
earthed position;
Figure 4-8 shows the busbar position;
repeat this procedure for the other two phases.
2.
If the panel is not in neutral position, put it in this
position now, see section 4.2.1.
3.
Turn the selector anti-clockwise, the control point of
the switch (5) is revealed.
4.
Use the built-in voltage detector to check that the
cable is dead.
Arrows and dots visible:
Detector is functioning correctly and the cable
is live;
Arrows and dots not visible: cable is dead.
N
OTE
The visible dot shows that the detector is
functioning correctly in accordance with the
demands for voltage detecting systems as
described in VDE 0682 art. 415.
This is a continuous internal function check.
Figure 4-7: Change-over switch in the earthed
position
Figure 4-8: Change-over switch in the busbar
position
Summary of Contents for Xiria
Page 39: ...Xiria 994 570 G01 06 39 APPENDIX 1 FLOOR PLANS ...
Page 40: ...Xiria 40 994 570 G01 06 ...
Page 41: ...Xiria 994 570 G01 06 41 ...
Page 42: ...Xiria 42 994 570 G01 06 ...
Page 43: ...Xiria 994 570 G01 06 43 ...
Page 44: ...Xiria 44 994 570 G01 06 ...
Page 45: ...Xiria 994 570 G01 06 45 APPENDIX 2 VOLTAGE DETECTING SYSTEM WEGA ...
Page 46: ...Xiria 46 994 570 G01 06 ...
Page 47: ...Xiria 994 570 G01 06 47 ...
Page 48: ...Xiria 48 994 570 G01 06 APPENDIX 3 ORION 3 0 ...
Page 49: ...Xiria 994 570 G01 06 49 APPENDIX 4 SHORT CIRCUIT INDICATOR ...
Page 55: ...Xiria 994 570 G01 06 55 ...
Page 56: ...Xiria 56 994 570 G01 06 ...