Xiria
994.570 G01 06
19
3.3.3
Replacing the cable connection cone
Damaged cable connection cones can be easily replaced
by our service department. A different type of cone can
also be fitted in the circuit-breaker panel at a later stage.
Two types are available, A and C in accordance with
EN 50181. Contact Eaton for further details.
3.3.4
Applying test current and test voltage
to the cable
If cable side voltage transformers are installed in the panel
make sure the primary cables are disconnected from the
pre-assembled connectors for the cable side voltage
transformers.
The unit is suitable as standard for the following test
voltages, for a maximum of 10 minutes per phase:
System
voltage
Test voltage
(DC or AC-peak value)
24 kV
60 kV
17.5 kV
45 kV
12 kV
30 kV
7.2 kV
30 kV
WARNING
Test accessories are needed to apply test current
and test voltage to the connected cables.
Figure 3-11
1. Primary cable
2. Pre-assembled connectors
1.
Earth the unit in accordance with section 4.2.2.
2.
Install the specified test accessories in accordance
with the instructions of the plug and test accessory
suppliers.
3.
The switch must not be activated until you and the
person responsible for the unit are satisfied that the
earthed connection can be opened safely with the
switch.
4.
The unit requires to be earthed again in accordance
with section 4.2.2 before the test accessories are
removed on completion of the work.
5.
Safety precautions:
The unit must be isolated from any possible normal
source of supply, other than the test device.
Under no circumstances must it be possible for the
unit to be powered up again by any source other
than the external supply used for voltage testing.
The applicable safety measures must be applied
with respect to all personnel present during voltage
testing.
1
2
Summary of Contents for Xiria
Page 39: ...Xiria 994 570 G01 06 39 APPENDIX 1 FLOOR PLANS ...
Page 40: ...Xiria 40 994 570 G01 06 ...
Page 41: ...Xiria 994 570 G01 06 41 ...
Page 42: ...Xiria 42 994 570 G01 06 ...
Page 43: ...Xiria 994 570 G01 06 43 ...
Page 44: ...Xiria 44 994 570 G01 06 ...
Page 45: ...Xiria 994 570 G01 06 45 APPENDIX 2 VOLTAGE DETECTING SYSTEM WEGA ...
Page 46: ...Xiria 46 994 570 G01 06 ...
Page 47: ...Xiria 994 570 G01 06 47 ...
Page 48: ...Xiria 48 994 570 G01 06 APPENDIX 3 ORION 3 0 ...
Page 49: ...Xiria 994 570 G01 06 49 APPENDIX 4 SHORT CIRCUIT INDICATOR ...
Page 55: ...Xiria 994 570 G01 06 55 ...
Page 56: ...Xiria 56 994 570 G01 06 ...