Xiria
52
994.570 G01 06
Voltage transformers:
The voltage transformers are mounted inside the
switchgear at the rear. They are connected with
preassembled internal primary cables to the circuit-
breaker in the most right panel (number 3). Also the choke
coil and the resistor for the anti ferro resonance filter
connected to the tertiary windings are mounted in this part
of the switchgear. The connections on the voltage
transformers are made with earth screened connectors
type A. The connections on the cable cones of the circuit-
breaker (panel 3) are made with earth screened
connectors type C, mounted in parallel with the
connectors for the primary cables. Due to the limited
mounting space inside the cable compartment these
connectors are make Tyco type RSTI 58 and RSTI CC58.
Current transformers:
The current transformers for metering and protection of
the circuit-breaker (panel 3) are mounted inside the cable
compartment around the primary cables. They are
mounted on a metal sub frame for easy
removing/remounting without disconnecting the secondary
wiring when the primary cables are mounted.
Voltage transformer
Connector type A on the voltage
transformer
Choke coil and resistor
(anti ferro resonance filter)
Current transformers for protection
Current transformers for metering
Primary cable clamps
Summary of Contents for Xiria
Page 39: ...Xiria 994 570 G01 06 39 APPENDIX 1 FLOOR PLANS ...
Page 40: ...Xiria 40 994 570 G01 06 ...
Page 41: ...Xiria 994 570 G01 06 41 ...
Page 42: ...Xiria 42 994 570 G01 06 ...
Page 43: ...Xiria 994 570 G01 06 43 ...
Page 44: ...Xiria 44 994 570 G01 06 ...
Page 45: ...Xiria 994 570 G01 06 45 APPENDIX 2 VOLTAGE DETECTING SYSTEM WEGA ...
Page 46: ...Xiria 46 994 570 G01 06 ...
Page 47: ...Xiria 994 570 G01 06 47 ...
Page 48: ...Xiria 48 994 570 G01 06 APPENDIX 3 ORION 3 0 ...
Page 49: ...Xiria 994 570 G01 06 49 APPENDIX 4 SHORT CIRCUIT INDICATOR ...
Page 55: ...Xiria 994 570 G01 06 55 ...
Page 56: ...Xiria 56 994 570 G01 06 ...