Xiria
20
994.570 G01 06
3.4 Connection of station earthing
The Xiria unit can be connected either to the left or to the
right of the station earthing. An earth bar, to which the
earth screens of the power cables and the system earth
can be connected, is located at the rear of every cable
connection compartment.
See Figure 3-12.
The earth bar is provided with 10 mm holes on both ends
outside the unit for the connection of the system earth.
Three M8 nuts are mounted on the earth bar in each cable
compartment for the connection of the earth screens of the
power cables.
3.5 Access to secondary compartment
The front plate requires to be removed in order to gain
access to the secondary compartment.
Procedure (standard)
1.
Remove the screws at the bottom of the front plate,
see Figure 3-13.
2.
Move the bottom of the front plate forward, lower it
and remove it, see Figure 3-14.
3.
The secondary compartment is now accessible.
Figure 3-12: Earth bar
Figure 3-13: Position of front plate fixing screws
Figure 3-14: Removing the front plate
Summary of Contents for Xiria
Page 39: ...Xiria 994 570 G01 06 39 APPENDIX 1 FLOOR PLANS ...
Page 40: ...Xiria 40 994 570 G01 06 ...
Page 41: ...Xiria 994 570 G01 06 41 ...
Page 42: ...Xiria 42 994 570 G01 06 ...
Page 43: ...Xiria 994 570 G01 06 43 ...
Page 44: ...Xiria 44 994 570 G01 06 ...
Page 45: ...Xiria 994 570 G01 06 45 APPENDIX 2 VOLTAGE DETECTING SYSTEM WEGA ...
Page 46: ...Xiria 46 994 570 G01 06 ...
Page 47: ...Xiria 994 570 G01 06 47 ...
Page 48: ...Xiria 48 994 570 G01 06 APPENDIX 3 ORION 3 0 ...
Page 49: ...Xiria 994 570 G01 06 49 APPENDIX 4 SHORT CIRCUIT INDICATOR ...
Page 55: ...Xiria 994 570 G01 06 55 ...
Page 56: ...Xiria 56 994 570 G01 06 ...