![Eaton US-S ESF30 28-P Mounting And Operating Instructions Download Page 87](http://html1.mh-extra.com/html/eaton/us-s-esf30-28-p/us-s-esf30-28-p_mounting-and-operating-instructions_525375087.webp)
87
8 Operating
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
Password:
deactivated
Password (6 digits)
<ok>
Menu 3.21:
Select the “deactivated” or “acti-
vated” setting with keys
Enter the password (the digits can
only be entered with keys F1, F2 or
F3)
Finish and return to Menu 3 with
<Menu>
Note:
When password protection is activate this prompt is only accessible when the cur-
rent password has already been entered. The prompt appears when a protected (sub)
menu is called in the main menu. The password is entered with keys F1=1, F2=2,
F3=3; a flashing square cursor marks the current entry point.
When password protection is active, all (sub)menus are protected from use without a
password, except:
– Menu 1 “Test & status menu”
– Menu 2 “Block, reset”.
Function keys
Optional inputs
Serialnumber & type
Password protection
etc....
Select the input point with keys
<ok>
Menu 3.20:
Line selection (1 - 3) with
Selection of the nominal operating
duration (1, 2, 3 or 8h) and limit oper-
ating duration (10 to 100%)
with keys
The nominal and limit operating du-
ration is the basis for the operating
duration test.
Finish and return to Menu 3 with
<Menu>
Connection to BMS
Function keys
Optional inputs
Serialnumber & type
etc....
Type: ZB-S
Nom. op. duration 3h
Limit op. duration 100%
Serial No:1234567/02
When “activated” is selected the pass-
word prompt also appears:
Password:
activated
Password (6 digits)
Password: 123231
Password:
1
<ok>
Menu 3.23:
Serialnumber & type
Password protection
Daylight saving time
Service info
This is a display with information about
the status of the installed controller
software (e.g. needed for enquiries with
CEAG Customer Service)
ATMega 128: Z480.F
Neuron RS485: Z481.0
Neuron FTT10A:Z410_0
go on with menu keys
<ok>
Menu 3.22:
Optional inputs
Serialnumber & type
Password protection
Daylight saving time
Service info
Summertime
(Sunday/Month)
Start: 0
/03
End:
0
/10
Selection of the settings with the
keys
Time to be set is the sunday of the
month where the change over of
summertime to wintertime effects.
Choice of the input field with
Finish and back to menu 3 with
<Menu>
Overview:
Main menu
Test & status menu
Block & reset alarms
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Logbooksetup
Send ServicePinMsg
Menu 3
Language
Date & time
Functiontest
Durationtest
Delay time mains
return
Manual reset
Selective EmgcyOper.
Relay setup
Buzzer setup
Display setup
Charger setup
Printer setup
Relay module setup
Webserver setup
Timer setup
Substation setup
Connection to BMS
Function keys
Optional inputs
Serialnumber & type
Password protection
Daylight saving time
Service info
Selection of
menu options
with the
keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes en-
tered are saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
NOTE
Factory setting = 100%
A change to the limit operating duration has to be
done by our customer service!