47
4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
International description
TC-L
Socket
2G11
Lamp power (W)
36
24
18
Luminous flux ratio (%)
100
59
43
100
73
57
46
100
71
52
47
Switch setting
0
5
9
0
3
6
9
0
3
7
9
Number of luminaires /
Current consumption from the
battery /
Apparent power
[A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA]
1
0�47 108 0�30 70 0�29 68 0�38 89 0�28 64 0�27 62 0�27 65 0�39 90 0�26 60 0�26 60 0�25 60
2
–
– 0�43 96 0�33 76
–
– 0�42 99 0�34 79 0�32 74
–
– 0�42 98 0�31 70 0�28 65
3
–
– 0�58 135 0�44 103 –
– 0�61 136 0�44 103 0�37 86
–
– 0�57 135 0�40 94 0�34 80
4
–
–
–
–
–
–
–
–
–
– 0�56 130 0�47 105 –
–
–
– 0�50 117 0�46 104
Table 3. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%) at
20 °C ambient temperature at the luminaire.
International
description
TC-D
Socket
G24Q1� G24Q2
Lamp power (W)
26
18
13
10
Luminous flux
ratio (%)
100
71
61
47
100
79
63
48
100
77
63
42
100
68
52
Switch setting
0
3
5
9
0
2
5
9
0
2
4
9
0
4
9
Number of
luminaires /
Current
consumption from
the battery /
Apparent power
[A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA]
1
0�36 85 0�28 63 0�27 61 0�27 64 0�30 51 0�26 37 0�24 29 0�23 24 0�26 60 0�26 49 0�21 49 0�21 49 0�25 58 0�21 49 0�20 44
2
– – 0�39 93 0�35 80 0�33 76 0�47 87 0�35 64 0�29 47 0�28 37 0�39 90 0�30 68 0�28 63 0�29 66 0�39 90 0�26 58 0�26 62
3
– – 0�54 126 0�45 104 0�36 80 0�65 114 0�48 86 0�36 65 0�32 48 0�53 121 0�41 91 0�32 73 0�30 71 0�54 125 0�31 74 0�30 70
4
– – – – 0�57 132 0�43 97 – – 0�60 106 0�44 81 0�34 62 – – 0�53 110 0�38 87 0�32 74 – – 0�38 88 0�32 72
5
– – – – – – – – – – 0�71 125 0�53 94 0�40 73 – – 0�57 130 0�48 103 0�33 76 – – 0�47 104 0�36 75
6
– – – – – – – – – – – – 0�60 108 0�44 83 – – – – 0�52 120 0�38 87 – – 0�54 121 0�40 81
7
– – – – – – – – – – – – – – – – – – – – 0�59 136 0�42 94 – – 0�59 137 0�45 94
Table 4. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%) at
20 °C ambient temperature at the luminaire.