Technical data
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
4.4.14 Webmodule
Conform to: EN 60950-1. Developed, manufactured and
tested acc. to ISO 9001.
Technical data
Supply voltage
24 V DC
Power consumption
1 W
Current consumption
33 mA +/- 25%
Connection
RJ45
Insulation class
III
Degree of protection acc�
to EN 60529
IP 20
Ambient temperature
-10 °C �� +55 °C
Connection terminal
1�5 mm²
Weight
0,55 kg
Dimensions
90 x 35 x 32 mm
Description / Scope of application
The webmodule CG-S for visualisation and monitoring
of a ZB-S system, AT-S
+
system or of a LP-STAR system
(seperate mounting instructions) or via local ethernet
(LAN) with a customary WEB-browser (e. g. Internet
ExplorerTM). Integrated mail-client for a comfortable
and event based failure notification for up to 5 email
addressees. Password protected access accounts capable
of parametrisation.
Mounting
Pay attention to tempera-tures outside the permitted
range during operation. The permissible ambient
temperature may not exceed 55°C.
The module was designed for DIN rail mounting (2TE) to
be only mounted in the cabinet. An external mounting
outside the LP-STAR Unit is not permitted.
Electrical connection
Status/
Failure LED
+ -
PE
24 V DC from
DC/DC converter
Service
Pin
Connection
of the 6-pole
data cable to
the control
unit CSU
Network
connection
RJ45
Connection to the CU (ZB-S / AT-S
+
)
To connect the webmodules Six-pole data cable to the
CU, the housing of the CU must be opened via both
spring retainers.
The plug of the Six-pole data cable must be connected
to the circuit board as shown in the photo below. Please
note the cable leading out of the housing.