4.
Close Source 1 Bypass MCCB; because the MCCB closes “around” the power switchelement, bypass is
transparent to the load.
5.
Open Source 1 input MCCB.
6.
Open the isolation MCSW(s): STS switching logic is bypassed.
88..33..33
H
Heellpp A
Assssiissttaannccee ffoorr B
Byyppaassss
The
Help
screen also has instructions to guide an operator through steps for going to Bypass 1 or 2 or returning
from either Bypass to Normal operation (
). When the system senses a step has been completed, the
Help screen proceeds to the next step. The Voice Unit also calls out each step as the operator executes the
procedure.