Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
66..22
EEtthheerrnneett C
Coonnnneeccttiioonn
The Monitor PCB has an Ethernet port and cable. The Ethernet cable hangs down from the Monitor with a an
RJ45 jack connection that is close to the Contractor Board.
Use the
Settings
screen to set Ethernet parameters (
). The Ethernet connection allows you to
run TCP/IP, Modbus TCP/IP, HTTP for the web server, SNMP, SNTP for time synchronization, and SMTP for
email summary alarm alerts.
describes configuration for these options.
66..33
D
Drryy C
Coonnttaacctt S
Siiggnnaallss
66..33..11
D
Drryy C
Coonnttaacctt O
Ouuttppuutt S
Siiggnnaallss
Contractor Board remote relays signal status and alarms through closed dry contacts, shown in
. There
are three predefined relay lists. Remote relays can be customized during setup to turn on for other points in the
STS points list.
Table 1. Output Dry Contact Signals, Remote Relays
Remote Relays
Basic Contractor Board
(Default List)
Enhanced Contractor Board
List 1
List 2
Relay 1
Summary Alarm
Summary Alarm
Summary Alarm
Relay 2
Load is on Source 1
Load is on Source 1
Load is on Source 1
Relay 3
Load is on Source 2
Load is on Source 2
Load is on Source 2
Relay 4
Output is OK
Source 1 is on Bypass
Source 1 is on Bypass
Relay 5
Not Available
Source 2 is on Bypass
Source 2 is on Bypass
Relay 6
Not Available
Source 1 is Available
STS cannot switch
Relay 7
Not Available
Source 2 is Available
Auto Retransfer is inhibited
Relay 8
Not Available
Output is OK
STS is on the Alternate Source
(not the Preferred Source)
NOTE
: Closed dry contacts signal the conditions shown in this table.
66..33..22
D
Drryy C
Coonnttaacctt IInnppuutt S
Siiggnnaallss
lists dry contact signals to the STS from an external source, such as the BMS.
•
Remote EPO
shuts down the STS.
•
Remote Select S1 or Remote Select S2
causes the STS to switch to that designated source.
•
Building Alarm 1-8
are input signals for various building sensors, such as fire, temperature, cooling failure,
or under floor water. The name of the Building Alarm is specified in the points list. A building alarm causes
a point to be activated in the points list, but causes no other action.