102
Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
1166..33
A
Annaalloogg A
Allaarrm
mss D
Deeffaauulltt S
Seettttiinnggss
Table 8. Voltage Alarms Default Settings
Voltage Alarms 600 Volt Points:
Parameter
High Limit
Setting
Low Limit
Setting
V phase-phase
110%
660
90%
540
V phase-neutral
110%
380
90%
311
Voltage Alarms 480 Volt Points:
Parameter
High Limit
Setting
Low Limit
Setting
V phase-phase
110%
528
90%
432
V phase-neutral
110%
305
90%
249
Voltage Alarms 208 Volt Points:
Parameter
High Limit
Setting
Low Limit
Setting
V phase-phase
110%
229
90%
187
V phase-neutral
110%
132
90%
108
Table 9. Current Alarms Default Settings
Current Alarms
Current
High Limit
Setting
2000A
110%
2200
Table 10. KVA Alarms Default Settings 600V Unit
KVA Phase and KVA Total Alarms for 600 Volt Unit
Current
Parameter
High Limit
Setting
Parameter
High Limit
Setting
2000A
KVA
110%
760
KVA total
110%
2283
Table 11. KVA Alarms Default Settings 480V Unit
KVA Phase and KVA Total Alarms for 480 Volt Unit
Current
Parameter
High Limit
Setting
Parameter
High Limit
Setting
2000A
KVA
110%
610
KVA total
110%
1830
Table 12. KVA Alarms Default Settings 208V Unit
KVA Phase and KVA Total Alarms for 208 Volt Unit
Current
Parameter
High Limit
Setting
Parameter
High Limit
Setting
2000A
KVA
110%
265
KVA total
110%
793