![background image](http://html1.mh-extra.com/html/eaton/sts-2000a/sts-2000a_installation-and-operation-manual_4182300109.webp)
Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
93
Table 7. Analog Screen Points (Continued)
Name
Units
Value
Index
Value Scale
Low Alarm
Index
High Alarm
Index
PDU 1 Total %KVA
%
113
68=68%
273
644
PDU 1 KW A
KW
114
None
274
645
PDU 1 KW B
KW
115
None
275
646
PDU 1 KW C
KW
116
None
276
647
PDU 1 Total KW
KW
117
None
277
648
PDU 1 PF A
%
118
*100 (92=0.92)
278
649
PDU 1 PF B
%
119
*100 (92=0.92)
279
650
PDU 1 PF C
%
120
*100 (92=0.92)
280
651
PDU 2 Volts AB
Volts
121
None
281
652
PDU 2 Volts BC
Volts
122
None
282
653
PDU 2 Volts CA
Volts
123
None
283
654
PDU 2 Volts AN
Volts
124
None
284
655
PDU 2 Volts BN
Volts
125
None
285
656
PDU 2 Volts CN
Volts
126
None
286
657
PDU 2 Amps A
Amps
127
None
287
658
PDU 2 Amps B
Amps
128
None
288
659
PDU 2 Amps C
Amps
129
None
289
660
PDU 2 KVA A
KVA
130
None
290
661
PDU 2 KVA B
KVA
131
None
291
662
PDU 2 KVA C
KVA
132
None
292
663
PDU 2 Total KVA
KVA
133
None
293
664
PDU 2 Peak Total KVA
KVA
134
None
294
665
PDU 2 %KVA A
%
135
68=68%
295
666
PDU 2 %KVA B
%
136
68=68%
296
667
PDU 2 %KVA C
%
137
68=68%
297
668
PDU 2 Total %KVA
%
138
68=68%
298
669
PDU 2 KW A
KW
139
None
299
670
PDU 2 KW B
KW
140
None
300
671
PDU 2 KW C
KW
141
None
301
672
PDU 2 Total KW
KW
142
None
302
673
PDU 2 PF A
%
143
*100 (92=0.92)
303
674
Summary of Contents for STS 2000A
Page 8: ......