System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
65
Schedule Sources
Parameter
Setting
SA Num
Type the number (from the
Smart Alarm States
table) of the
Smart Alarm
for
which this source is an input.
Status
Set to
Enabled
.
First Activation
Set to the date and time when the
Schedule Source
will activate for the first time
(see the diagram below).
Duration
Set to the length of time that the
Schedule Source
will remain active each time it
activates (see the diagram below).
Interval
Set to the time interval between the start of each activation (see the diagram
below).
Number of
Activations
Set the number of activations.
If set to zero then there is no limit to the number of activations.
Invert
The source is inverted before it is used to trigger the
Smart Alarm.
The
Smart
Alarm
will be triggered when the source becomes inactive.
Trigger
Specify how the source is used to trigger the
Smart Alarm.
Level –
triggered as long as the source is active.
Edge Set
– triggered when the source becomes active
.
Edge Reset
– triggered when the source becomes inactive
Edge Latch –
triggered when the source becomes active. The Smart Alarm
remains active as long as the source is active.
Scheduled Sources Operation
Duration
Interval
Active
Inactive
First
Date/Time
Time
1
2
3
4
Activation
number