System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
95
Configuration
Set the following parameters.
Parameter
Description
Where to find:
Name
User-specified energy meter name.
SC300: Not available.
DCTools: Meters
Web:
Web:
Applications > Energy
Metering > Meter Names
Group
Set to 0.
Analog Input
Meter Number
The meter that uses this analog input value.
SC300: Not available.
DCTools: Meters
Web:
Applications > Energy
Metering > Meter
Configuration > Analog
Inputs
Analog input
number
The analog input value that is used in this meter.
Function
Tells the SC300 whether to treat this value as a
voltage (V), current (A), or power (W or kW) for
the power calculation.
System Value
Meter Number
The meter that uses this system value.
SC300: Not available.
DCTools: Meters
Web:
Applications > Energy
Metering > Meter
Configuration > System
Value Inputs
System Input
The System Value Input that is used in this
meter.
Index
The System Value Index, where appropriate.
For instance, Power Meter 1
Power Gain
This is a scaling factor applied to the power
input value. Use this where the input has to be
multiplied by a constant value.
SC300: Not available.
DCTools: Meters
Web:
Applications > Energy
Metering > Meters
Power Offset
This is an offset applied to the power input
value.