6.1.1.1 Set Device Instance for each Lighting Panel Attached to the Device
The Device Instance can be set independently of the site administrator.
As an example:
A Device Instance is a BACnet Node-ID which is obtained by the network administrator.
Each lighting panel connected to the Device will have its own BACnet Device Instance.
The values allowed for a BACnet Device Instance can range from 1 to 4,194,303.
With the default BACnet Device Instance value of 50,000 the Device Instances values generated
will be within the range of 50,000 plus the incremental number of lighting panels that are
connected to the ProtoAir. The first lighting panel will therefore be 50,000.
To assign a specific Device Instance (or range); change the Device instance value to assigned
value of the first lighting panel.
The Web Configurator will be displayed as the landing page.
Figure 14: BACnet/IP Settings Window