Eaton ProtoAir Start-Up Guide 

Page 22 of 66 

o

 

By clicking on a light panel, parameters for that panel will be shown. 

 

 

o

 

Clicking on a light displays and allows editing of the preconfigured BACnet parameters. 

 

 

 

Once the items for configuration are chosen, click on the 

“Save Configuration” button. The save 

configuration progress bar will appear. This process may take several minutes. 

 

 

 

 

 

 

 

 

Figure 23: Saving Configuration Bar 

Figure 21: View Light Panel Parameters 

Figure 22: View & Edit BACnet Parameters on a Lighting Panel 

Summary of Contents for ProtoAir FPA-W34

Page 1: ...Guide For Interfacing Eaton Products Greengate iLumin and Fifth Light To Building Automation Systems BACnet MS TP BACnet IP Modbus TCP IP and Modbus RTU APPLICABILITY EFFECTIVITY Explains ProtoAir har...

Page 2: ...t of the ProtoAir product SMC does not provide direct support If Eaton needs to escalate the concern they will contact Sierra Monitor Corporation for assistance Support Contact Information Eaton Light...

Page 3: ...ector Section 4 2 5 Connect a PC to the ProtoAir via Ethernet cable and change the IP Address of the PC to the same subnet as the ProtoAir Set the IP Address of the ProtoAir to the subnet of the inten...

Page 4: ...otoAir 20 6 3 Fifth Light System Status 24 7 BACnet Setting Device Instance Offset to Assign Specific Device Instances 26 8 Using the Embedded BACnet Explorer 27 8 1 Discover Device List 28 8 2 View D...

Page 5: ...ndix C Vendor Information Eaton 49 Appendix C 1 3264640000 Greengate Mappings to BACnet and Modbus 49 Appendix C 2 4864643204 Greengate Mappings to BACnet and Modbus 51 Appendix C 3 808640000 Greengat...

Page 6: ...Edit BACnet Parameters on a Lighting Panel 22 Figure 23 Saving Configuration Bar 22 Figure 24 Saved Configuration 23 Figure 25 Clear Configuration Window 23 Figure 26 Fifth Light Landing Page System S...

Page 7: ...rotoAir Start Up Guide List of Figures Figure 50 DIN Rail 46 Figure 51 ProtoAir FPA W34 Dimensions 47 Figure 52 Kaspersky ES10 Settings 48 Figure 53 Web Anti Virus Trusted URLs 48 Figure 54 Specificat...

Page 8: ...t indicates that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing...

Page 9: ...iscover any of Eaton s products hereafter called device connected to the ProtoAir and automatically configures them for BACnet MS TP BACnet IP Modbus TCP IP or Modbus RTU It is not necessary to downlo...

Page 10: ...t Count Capacity Greengate Devices Point Count Per Device 3264640000 161 4864643204 213 808640000 81 344640003 115 1664643204 181 6464643200 225 Figure 3 Greengate Point Count per Device iLumin Device...

Page 11: ...g to BACnet IP network If the ProtoAir is the last device on the Serial trunk then the End Of Line Termination Switch needs to be enabled Figure 6 o The default setting from the factory is OFF switch...

Page 12: ...margin should be added to the power supply of the host system A safety margin of 25 is recommended Figure 7 Required Current Draw for the ProtoAir Apply power to the ProtoAir as shown below in Figure...

Page 13: ...nd ProtoAir The default IP Address for the ProtoAir Ethernet connection is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and ProtoAir are on different IP networks assign a static IP Address to t...

Page 14: ...the ProtoAir Install the FS Toolbox application from the USB drive or get it from the Sierra Monitor website Use the FS Toolbox to find the ProtoAir IP Address and connect for configuration NOTE If th...

Page 15: ...lt address is 192 168 1 24 o The Select System Page will appear the first time the FieldServer is accessed Select the desired protocol The Web Configurator landing page will now appear NOTE If the wro...

Page 16: ...ld If necessary change the IP Gateway Default Gateway field NOTE If the ProtoAir is connected to a managed switch router the IP Gateway of the ProtoAir should be set to the IP Address of that managed...

Page 17: ...OAIR 6 1 Select BMS Protocol Going back to the Discovery and Configuration tab and press BMS Settings button to view change the Building Management System BMS Settings Select BACnet IP BACnet MS TP Mo...

Page 18: ...nstance The values allowed for a BACnet Device Instance can range from 1 to 4 194 303 With the default BACnet Device Instance value of 50 000 the Device Instances values generated will be within the r...

Page 19: ...128 to 255 Addresses from 128 to 255 are Slave Addresses and can not be discovered by BMS Front Ends that support auto discovery of BACnet MS TP devices Enter the following details into the web config...

Page 20: ...scovery button to enter the port network address panel address and number of panels for the device For iLumin click on the Start Discovery button to enter the port network address and iLumin config fi...

Page 21: ...ry process is complete the discovery tree will immediately come up The items being marked as green indicate that they have not been configured for protocol conversion o When clicking on gateways or ga...

Page 22: ...lows editing of the preconfigured BACnet parameters Once the items for configuration are chosen click on the Save Configuration button The save configuration progress bar will appear This process may...

Page 23: ...to clear a configuration click on the Clear Configuration button An additional option to clear all other device configurations will appear After clicking on the Clear Restart button the window will s...

Page 24: ...th Light Panel manual The ProtoAir allows BMS settings to be changed BBMD settings Public IP Address Public IP Port Router Network Number Network Number and IP Port and Fifth Light Panel system inform...

Page 25: ...Eaton ProtoAir Start Up Guide Page 25 of 66 Click the Switch to another product button to clear the current configuration and restart Figure 28 Switch to Another Product...

Page 26: ...ice Instance or range change the Device Instance Offset value as needed using the calculation below Device Instance desired Offset Node_ID NOTE Node_ID is gathered from the Eaton device For example if...

Page 27: ...login to the BACnet Explorer page using the supplied username and password NOTE The default user name is admin and default password is admin NOTE For BACnet IP click on the Configuration button on the...

Page 28: ...of the screen to go to the BACnet Explorer page To discover the devices connected to the same subnet as the BACnet Explorer click the Discover button binocular icon This will open the Discovery windo...

Page 29: ...a green message to appear in the upper right corner of the browser to confirm that the action is complete 8 2 View Device Details and Explore Points Parameters To view the device details click the blu...

Page 30: ...ing the device directly in Figure 37 50001 and click the Explore button or double click the device object o Now additional device details are viewable however the device can be explored even further C...

Page 31: ...cted since the last explore simply press the Refresh button that appears on the upper right side of the screen when highlighting individual properties to refresh all the values NOTE The Explorer Searc...

Page 32: ...table such as object name object description etc however this is not recommended because the BACnet Explorer is a discovery tool not a Building Management System BMS To edit the present value select i...

Page 33: ...of 66 Enter the appropriate change and click write A check will appear inside the save button and the window will close When the BACnet Explorer page appears the present value will be changed as spec...

Page 34: ...er Configuration Add TLS_Port parameter in the connections section of the configuration file and set to a port number between 1 65535 Connections Adapter Protocol TLS_Port N1 Modbus TCP 1502 This conf...

Page 35: ...FieldServer with the following connection settings Connections Adapter Protocol TLS_Port Validate_Client_Cert Cert_Authority_File N1 Modbus TCP 1502 Yes my_authorized_clients pem This configuration ha...

Page 36: ...nymously known as common name host name or domain etc The common name can be obtained by the following methods Ask the certificate issuer for the host name Use online tools to decode the certificate f...

Page 37: ...ertificate against its own internal authority file before finalizing the connection By default this means the FieldServer will only establish connections to other FieldServers Remote_Node_TLS_Port Val...

Page 38: ...in the PC s Device Manager List and that it is configured to run the Modbus TCP IP protocol Check that the IP netmask of the PC matches the ProtoAir The Default IP Address of the ProtoAir is 192 168 1...

Page 39: ...e file and complete the installation Connect a standard CAT5 Ethernet cable between the user s PC and ProtoAir Double click on the FS Toolbox Utility and click Discover Now on the splash page Check fo...

Page 40: ...Settings No COMS on Greengate iLumin or Fifth Light side Check the following Check Greengate iLumin or Fifth Light IP Address Check Ethernet switch and cable Check Ethernet LEDs Appendix B 5 Verify de...

Page 41: ...he RX LED will flash when a message is sent on the serial port on the 3 pin connector If the serial port is not used this LED is non operational Figure 45 Diagnostic LEDs Appendix B 6 Before Contactin...

Page 42: ...Ethernet cable between the PC and ProtoAir Double click on the FS Toolbox Utility Step 1 Take a Log o Click on the diagnose icon of the desired device o Ensure Full Diagnostic is selected this is the...

Page 43: ...d is finished the Diagnostic Test Complete window will appear Step 2 Send Log o Once the diagnostic test is complete a zip file will be saved on the PC o Click Open to launch explorer and have it poin...

Page 44: ...do the following a Click on Setup b Click on File Transfer c Click on the Firmware tab 5 In the Firmware tab click on Choose Files and select the firmware file extracted in step 1 6 Click on the oran...

Page 45: ...stricted access to the ProtoAir The User account can view any ProtoAir information but cannot make any changes or restart the ProtoAir The password needs to be a minimum of eight characters and is cas...

Page 46: ...Eaton ProtoAir Start Up Guide Page 46 of 66 Appendix B 10 Mounting The ProtoAir can be mounted using the DIN rail mounting bracket on the back of the unit Din Rail Bracket Figure 50 DIN Rail...

Page 47: ...Eaton ProtoAir Start Up Guide Page 47 of 66 Appendix B 11 Physical Dimensions for FPA W34 P1 Serial Port Power Port Figure 51 ProtoAir FPA W34 Dimensions...

Page 48: ...e needs to be modified to allow the PC to register bridges on FieldPoP NOTE This problem is specific to KES10 Kaspersky 2017 does not have this problem To fix the problem the ProtoAir http 192 168 100...

Page 49: ...22 22 Relay023 BV 23 23 Relay024 BV 24 24 Relay025 BV 25 25 Relay026 BV 26 26 Relay027 BV 27 27 Relay028 BV 28 28 Relay029 BV 29 29 Relay030 BV 30 30 Relay031 BV 31 31 Relay032 BV 32 32 Remote01 BV 1...

Page 50: ...emote059 BV 159 159 Remote060 BV 160 160 Remote061 BV 161 161 Remote062 BV 162 162 Remote063 BV 163 163 Remote064 BV 164 164 Switch01 BI 1 10001 Switch02 BI 2 10002 Switch03 BI 3 10003 Switch04 BI 4 1...

Page 51: ...h060 BI 60 10060 Switch061 BI 61 10061 Switch062 BI 62 10062 Switch063 BI 63 10063 Switch064 BI 64 10064 Appendix C 2 4864643204 Greengate Mappings to BACnet and Modbus Point Name BACnet Object Type B...

Page 52: ...emote015 BV 115 115 Remote016 BV 116 116 Remote017 BV 117 117 Remote018 BV 118 118 Remote019 BV 119 119 Remote020 BV 120 120 Remote021 BV 121 121 Remote022 BV 122 122 Remote023 BV 123 123 Remote024 BV...

Page 53: ...19 10019 Switch020 BI 20 10020 Switch021 BI 21 10021 Switch022 BI 22 10022 Switch023 BI 23 10023 Switch024 BI 24 10024 Switch025 BI 25 10025 Switch026 BI 26 10026 Switch027 BI 27 10027 Switch028 BI 28...

Page 54: ...0119 AI_State020 BI 120 10120 AI_State021 BI 121 10121 AI_State022 BI 122 10122 AI_State023 BI 123 10123 AI_State024 BI 124 10124 AI_State025 BI 125 10125 AI_State026 BI 126 10126 AI_State027 BI 127 1...

Page 55: ...BV 135 135 Remote036 BV 136 136 Remote037 BV 137 137 Remote038 BV 138 138 Remote039 BV 139 139 Remote040 BV 140 140 Remote041 BV 141 141 Remote042 BV 142 142 Remote043 BV 143 143 Remote044 BV 144 144...

Page 56: ...0 Remote021 BV 121 121 Remote022 BV 122 122 Remote023 BV 123 123 Remote024 BV 124 124 Remote025 BV 125 125 Remote026 BV 126 126 Remote027 BV 127 127 Remote028 BV 128 128 Remote029 BV 129 129 Remote030...

Page 57: ...BI 23 10023 Switch024 BI 24 10024 Switch025 BI 25 10025 Switch026 BI 26 10026 Switch027 BI 27 10027 Switch028 BI 28 10028 Switch029 BI 29 10029 Switch030 BI 30 10030 Switch031 BI 31 10031 Switch032 B...

Page 58: ...3 BV 123 123 Remote024 BV 124 124 Remote025 BV 125 125 Remote026 BV 126 126 Remote027 BV 127 127 Remote028 BV 128 128 Remote029 BV 129 129 Remote030 BV 130 130 Remote031 BV 131 131 Remote032 BV 132 13...

Page 59: ...Switch028 BI 28 10028 Switch029 BI 29 10029 Switch030 BI 30 10030 Switch031 BI 31 10031 Switch032 BI 32 10032 Switch033 BI 33 10033 Switch034 BI 34 10034 Switch035 BI 35 10035 Switch036 BI 36 10036 Sw...

Page 60: ...126 10126 AI_State027 BI 127 10127 AI_State028 BI 128 10128 AI_State029 BI 129 10129 AI_State030 BI 130 10130 AI_State031 BI 131 10131 AI_State032 BI 132 10132 AI01 AI 1 30001 AI02 AI 2 30002 AI03 AI...

Page 61: ...lay058 BV 58 58 Relay059 BV 59 59 Relay060 BV 60 60 Relay061 BV 61 61 Relay062 BV 62 62 Relay063 BV 63 63 Relay064 BV 64 64 Remote01 BV 101 101 Remote02 BV 102 102 Remote03 BV 103 103 Remote04 BV 104...

Page 62: ...ote062 BV 162 162 Remote063 BV 163 163 Remote064 BV 164 164 Switch01 BI 1 10001 Switch02 BI 2 10002 Switch03 BI 3 10003 Switch04 BI 4 10004 Switch05 BI 5 10005 Switch06 BI 6 10006 Switch07 BI 7 10007...

Page 63: ...3 Switch064 BI 64 10064 AI_State01 BI 101 10101 AI_State02 BI 102 10102 AI_State03 BI 103 10103 AI_State04 BI 104 10104 AI_State05 BI 105 10105 AI_State06 BI 106 10106 AI_State07 BI 107 10107 AI_State...

Page 64: ...o BACnet and Modbus Point Name BACnet Object Type BACnet Object ID Modbus Register scene AO 1 40001 sceneFT AO 2 40002 Appendix C 8 Channel iLumin Mappings to BACnet and Modbus Point Name BACnet Objec...

Page 65: ...ix D 1 1 Compliance with UL Regulations For UL compliance the following instructions must be met when operating ProtoAir The units shall be powered by listed LPS or Class 2 power supply suited to the...

Page 66: ...n or on which original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from batter...

Reviews: