Read/write function block data
For more information visit:
www.EatonElectrical.com
MN05013001E
81
Timing relays: T1 – T16
Telegram structure
Byte
Meaning
Value (hex), sent by
Master
Slave
0
Toggle byte
J
page 44
1
Command:
Read
89
–
Write
8D
–
Response:
Read successful
–
C2
Write successful
–
C1
Command rejected
–
C0
1
2
Type
8E
8E
3
Instance
2
00 – 0F
00 – 0F
4
Index
J
Table 33
5 – 8
Data 1 – 4
depending on index
J
Table 34
1) Possible causes
J
page 91
2) EZ provides 16 timing relays T1 to T16 for use as required. These can
be addressed using the instance (0 – F).