Read/write function block data
For more information visit:
www.EatonElectrical.com
MN05013001E
151
Table 84: Operand overview
Table 85: Index 0 – Bit IO
Index
(hex)
Operand
Read
Write
00
Bit IO,
J
Table 85
×
01
Mode/Parameter
–
–
02
Input value, value range: –32768 to +32767
I1
×
c
1
03
Recovery time [0.1 s], Value range: 0 to 65535
TG
×
c
1
04
Proportional gain [%], Value range: 0 to 65535
KP
×
c
1
05
Delayed output value,
value range: –32768 to +32767
QV
×
1) The value can only be written if it is assigned to a constant in the program.
Bit 7 6 5 4 3
2
1
0
FB output Data 3
– – – – –
–
–
EN
1
1) Activates the function block on status 1.