For more information visit:
www.EatonElectrical.com
Appendix
MN05013001E
188
Ambient mechanical conditions
Electromagnetic compatibility (EMC)
Pollution degree
2
Degree of protection
EN 50178
IEC 60529 VBG4
IP20
Oscillations
IEC 60068-2-6
10 to 57 Hz (constant
amplitude 0.15 mm)
57 to 150 Hz (constant
acceleration 2 g)
Shocks
IEC 60068-2-27
18 shocks
(semi-sinusoidal 15 g/11 ms)
Drop
IEC 60068-2-31
Drop height 50 mm
Free fall, packaged
IEC 60068-2-32
1 m
Electrostatic discharge
IEC/EN 61000-4-2, degree of
severity 3
8 kV air discharge,
6 kV contact discharge
Electromagnetic fields
IEC/EN 61000-4-3
Field strength 10 V/m
Radio interference suppression
EN 55011, EN 55022
Limit class A
Burst
IEC/EN 61000-4-4, degree of
severity 3
2 kV supply lines, 1 kV signal
lines
High-energy pulses (surge)
EZ...-DC...
IEC/EN 61000-4-5, degree of
severity 2
0.5 kV power cable
symmetrical
Line-conducted interference
IEC/EN 61000-4-6
10 V