EZ800/EZD Control Commands
MN05013001E
148
Table 81: Operand overview
Index
(hex)
Operand
Read
Write
00
Bit IO,
J
Table 82
×
01
Mode,
J
Table 83
×
02
Setpoint: –32768 to +32767
I1
×
c
1
03
Actual value: –32768 to +32767
I2
×
c
1
04
Proportional gain
[%], Value range: 0 to 65535
KP
×
c
1
05
Reset time [0.1 s], Value range: 0 to 65535
TN
×
c
1
06
Rate time [0.1 s], Value range: 0 to 65535
TV
×
c
1
07
Scan time = Time between function block calls.
Value range: 0.1s to 6553.5s.
If 0 is entered as the value, the scan time will be determined
by the program cycle time.
TC
×
c
1
08
Manual manipulated variable, value range: –4096 to +4095 MV
×
c
1
09
Manipulated variable
QV
×
• Mode: UNI, value range: 0 to +4095 (12 bit)
• Mode: BIP, value range: –4096 to +4095 (13 bit)
1) The value can only be written if it is assigned to a constant in the program.
J
The data for index 2 and 9 is transferred as a 32-bit value in
Intel format (Data 1 – Low Byte .. Data 2 - High Byte).