Connecting PROFIBUS-DP
For more information visit:
www.EatonElectrical.com
MN05013001E
19
Connecting PROFIBUS-DP
Use a 9-pole SUB-D plug to connect the PROFIBUS-DP
interface to the PROFIBUS-DP fieldbus. For this use the
special PROFIBUS-DP plug and the special PROFIBUS-DP
cable available from the Eaton range of accessories. The type
of cable used determines the permissible maximum bus
length and the transfer rate.
PROFIBUS-DP connection
assignment
Connections 3, 8 and the shield are sufficient for data transfer.
Pin
Signal name
Designation
1
Not assigned
-
2
Not assigned
-
3
RxD/TxD-P (B Line)
Receive/Send data P
4
CNTR-P / RTS
Request to Send
5
DGND
Data reference potential
6
VP
+5V DC for external bus connection
7
Not assigned
-
8
RxD/TxD-N (A-
Line)
Receive/Send data N
9
Not assigned
-
6
7
8
9
2
3
4
5
1
4
3
8
5
6
CNTR-P
RxD/TxD-P (B/B')
RxD/TxD-N (A/A')
DGND
VP