49
Chapter 5 - Fan control application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN
—September 2021 www.eaton.com
Control I/O configuration
•
Run 240 Vac and 24 Vdc control wiring in separate conduit.
•
Communication wire to be shielded.
Table 21. Fan application default I/O connection.
DM1
External wiring Terminal Short name Name
Default setting
Description
Res
1
DI1
Digital input 1
Run forward
Starts the motor in the forward direction.
2
DI2
Digital input 2
Run reverse
Start the motor in the reverse direction.
3
DI3
Digital input 3
External fault
Triggers a fault in the drive.
4
DI4
Digital input 4
Fault reset
Resets active faults in the drive.
5
CMA
DI1 to DI4 common
Grounded
Allows for sourced input.
6
A
RS-485 signal A
—
Fieldbus communication (Modbus RTU, BACNet).
7
B
RS-485 signal B
—
Fieldbus communication (Modbus RTU, BACNet).
8
AI1+
Analog input 1
0 - 10 V
Voltage speed reference (programmable to 4 mA to 20 mA).
9
AI1-
Analog input 1 ground
—
Analog input 1 common (ground).
10
GND
I/O signal ground
—
I/O ground for reference and control.
11
AO1+
Analog output 1
Output frequency
Shows output frequency to motor 0 - 60 Hz (4 mA to 20 mA).
12
GND
I/O signal ground
—
I/O ground for reference and control.
13
10 V
10 Vdc reference output
10.3 Vdc +/- 3%
10 Vdc reference voltage.
14
24 V
24 Vdc control output
24 Vdc In/Out
Control voltage input/output (100 mA max.).
18
R1NO
Relay 1 normally open
Run
Changes state when the drive is in the run state.
19
R1CM
Relay 1 common
20
R1NC
Relay 1 normally closed
Default
Default