background image

239

 

Application notes

POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE

    

MN040049EN

—September 2021   www.eaton.com

Application notes

Faults and warning codes

Under this menu, you can find active faults, history faults, and fault codes.

Table 72.  Active faults. 

Menu

Function

Note

Active faults

When a fault/faults appear(s), the display with the name 

and fault time of the fault will be pop.  Press DETAIL to see 

the fault data.

The active faults submenu shows the list of faults.  Select 

the fault and push DETAIL to see the fault data.

The fault remains active until it is cleared with the Reset  

button push for 2s) or with a reset signal from the I/O terminal  

or fieldbus.

The memory of active faults can store the maximum of 10 faults in 

the order of appearance.

Table 73.  History faults.

Menu

Function

Note

History faults

10 latest faults are stored in the fault history.  Select the 

fault and push DETAIL to see the fault data.

The history fault will be stored until it is cleared with the  

OK button (push for 5 s).

The memory of active faults can store the maximum of 10 faults in 

the order of appearance.

Fault codes and descriptions

Configurable 1 = The fault type of this fault is configurable, fault type can be configured as: 

0 = No action; 1 = Warning; 2 = Fault; 3= Fault, Coast.

Fault 

code

Fault name/

description

Fault type

Default 

configuration Possible cause

Remedy

1

Over current

Fault

AC drive has detected too high a current (>4*IH) in the motor 

cable: 

• Sudden heavy load increase;

• Short circuit in motor cables;

• Unsuitable motor.

• Check loading.

• Check motor.

• Check cables and connections.

• Make identification run.

• Check ramp times.

2

Over voltage

Fault

The DC-link voltage has exceeded the limits defined:

• Too short a deceleration time;

• Brake chopper is disabled;

• High overvoltage spikes in supply;

• Start/stop sequence too fast.

• Make deceleration time longer.

•  Use brake chopper or brake resistor 

(available as options).

• Activate overvoltage controller.

• Check input voltage.

3

Earth fault

Fault

Configurable

Current measurement has detected that the sum of motor 

phase current is not zero:

• Insulation failure in cables or motor.

• Check motor cables and motor.

9

Under voltage

Fault

Configurable

DC link voltage is under the voltage limits defined:

• Most probable cause:  Too low a supply voltage;

• AC drive internal fault;

• Defect input fuse;

• External charge switch not closed.

Note:

 This fault is activated only if the drive is in the Run 

state.

•  In case of temporary supply voltage 

break reset the fault and restart the 

AC drive.  Check the supply voltage.  

If it is adequate, an internal failure 

has occurred.  Contact the distributor 

near you.

10

Input phase 

superv

No action

Configurable

Input line phase is missing.

•  Check supply voltage, fuses, and 

cable.

11

Output phase 

superv

Fault

Configurable

Current measurement has detected that there is no current in  

one motor phase.

Check motor cable and motor.

13

Drive under 

temp

Warning

Configurable

Too low temperature measured in power.

Unit’s heat sink or board.  Heat sink temperature is under 

-10°C.

14

Drive over temp Fault

Too high temperature measured in power.

Unit’s heat sink or board.  Heat sink temperature is over 90°C.

•  Check the correct amount and flow of 

cooling air.

• Check the heat sink for dust.

• Check the ambient temperature.

•  Make sure that the switching 

frequency is not too high in relation to 

ambient temperature and motor load.

15

Motor stalled

No action

Configurable

Motor is stalled.

Check motor and load.

Summary of Contents for PowerXL DM1 Series

Page 1: ...PowerXL DM1 Series VFD Effective September 2021 Application manual Original instructions Supports Firmware Version Bundle V1 04 and V1 05...

Page 2: ...MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOM...

Page 3: ...duct information You can also find information on local distributors or Eaton s sales offices Website address www eaton com drives EatonCare customer support center Call the EatonCare Support Center i...

Page 4: ...igh voltage viii Warnings and cautions viii CHAPTER 1 POWERXL DM1 SERIES OVERVIEW 1 How to use this manual 1 Rating label 1 Carton labels U S and Europe 2 CHAPTER 2 KEYPAD OVERVIEW 3 Main keypad butto...

Page 5: ...230 Faults and warning codes 230 Fault codes and descriptions 230 Recommended secure hardening guidelines 234 References 236 List of figures Figure 1 Rating label 1 Figure 2 Carton rating label 2 Fig...

Page 6: ...2 Table 20 Fan application default I O connection 46 Table 21 Monitor 47 Table 22 Parameters 49 Table 23 Inputs 51 Table 24 Outputs 59 Table 25 Drive control 61 Table 26 Motor control 64 Table 27 Prot...

Page 7: ...pump status 142 Table 55 Multi pump measurement 145 Table 56 Parameters 148 Table 57 Inputs 150 Table 58 Outputs 165 Table 59 Drive control 174 Table 60 Motor control 180 Table 61 Protections 184 Tabl...

Page 8: ...abit to use only one hand when checking components Always work with another person in case an emergency occurs Disconnect power before checking controllers or performing maintenance Be sure equipment...

Page 9: ...ective device must be provided as required by the National Electric Code NEC Failure to follow this precaution may result in death or severe injury WARNING This drive can cause a DC current in the pro...

Page 10: ...to follow these precautions may cause death or severe injury WARNING The drive outputs U V W must not be connected to the input voltage or the utility line power as severe damage to the device may occ...

Page 11: ...this operating manual handy and distribute to all users technicians and maintenance personnel for reference Table 1 Common abbreviations Abbreviation Definition CT Constant torque with high overload r...

Page 12: ...2 Chapter 1 PowerXL DM1 series overview POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN September 2021 www eaton com Carton labels U S and Europe Figure 2 Carton rating label...

Page 13: ...er and navigation buttons With the control keypad it is possible to control the speed of a motor to supervise the state of the equipment and to set the frequency converter s parameters see Figure 3 Fi...

Page 14: ...s of control source Motor stop from the keypad Up Down Up and Down arrows Move either up or down a menu list to select the desired menu item Editing a parameter bit by bit while the active digit is sc...

Page 15: ...meter whole edit mode when this parameter can be written Enter parameter group mode Enter parameter mode from group mode Main keypad display The main keypad LCD display indicates the status of the mot...

Page 16: ...put P2 3 Preset Speed P2 4 AI Settings P3 Outputs P3 1 RO1 Function P3 3 Analog Output P4 Drive Control P4 1 Basic Settings P5 Motor Control P5 1 Basic Settings P6 Protections P6 1 Motor P6 2 Drive P6...

Page 17: ...and 11 buttons With the control keypad it is possible to control the speed of a motor to supervise the state of the equipment and to set the frequency converter s parameters Figure 6 Remote keypad an...

Page 18: ...ressing this button more than 2 seconds in any page Hold Stop and Back Reset for 5 seconds to return drive to factory default At Main Menu page pressing Back Reset takes the user to the Default page L...

Page 19: ...including 5 seconds in any page This button is used in the parameter edit mode to save the parameter setting To confirm the start up list at the end of the Start Up Wizard To confirm the comparison it...

Page 20: ...ve is not ready or does not have a signal FIM is displayed to indicate it is in Fire Mode and the drive is in a Run state TFM is displayed when in the Fire Mode Test Mode and the drive is in a Run Sta...

Page 21: ...SERIES VARIABLE FREQUENCY DRIVES MN040049EN September 2021 www eaton com Menu navigation remote keypad This section provides basic instruction on navigating each section in the menu structure from the...

Page 22: ...password function When the password function is enabled the user will be prompted to enter a password before application changes parameter value changes or password changes By default the password fun...

Page 23: ...e 0 30 Maximum value 1 00 Default value 0 85 Description Motor nominal nameplate full load power factor Find this value on the rating plate of the motor P1 9a Motor nominal voltage ID 487 Minimum valu...

Page 24: ...us or 3 Keypad Description Selects where the drive will look for the start command in the remote location I O terminals would be from the digital hard wired inputs fieldbus would be a communication bu...

Page 25: ...Default value N A Options 0 Disabled or 1 Enable Description Blue tooth enable a Parameter value can only be changed after the drive has stopped b Parameter value will be set to be default when changi...

Page 26: ...ntrol mode and tuning of the V Hz curve can be selected Drive Motor protections can be customized to defined actions for added user control Below is a list of other features that are available in the...

Page 27: ...CMA DI1 to DI4 common Grounded Allows for sourced input 6 A RS 485 signal A Fieldbus communication Modbus RTU BACNet 7 B RS 485 signal B Fieldbus communication Modbus RTU BACNet 8 AI1 Analog input 1...

Page 28: ...put 1 ground Analog input 1 common ground 10 GND I O signal ground I O ground for reference and control 11 AO1 Analog output 1 Output frequency Shows output frequency to motor 0 60 Hz 4 mA to 20 mA 12...

Page 29: ...meplate values and measured motor current M1 7 Motor voltage ID 6 Minimum value V Maximum value V Default value V Description Output ac motor voltage Vac M1 8 DC link voltage ID 7 Minimum value V Maxi...

Page 30: ...cription PI set point in process units M5 2 PI feedback ID 18 Minimum value Varies Maximum value Varies Default value Varies Description PI feedback level in process units M5 3 PI error value ID 20 Mi...

Page 31: ...cy parameter settings 1 Fire mode minimum frequency 2 Derag 3 MPFC staging frequency 4 MPFC master fixed frequency 5 Prime pump frequency 6 Prime pump frequency 2 P1 2b Maximum frequency ID 102 Minimu...

Page 32: ...rated frequency This value is found on the rating plate of the motor P1 11b Local control place ID 1695 Minimum value N A Maximum value N A Default value 0 Options 0 keypad 1 IO terminal or 3 fieldbu...

Page 33: ...DI closed contact start forward P2 2 3 DI closed contact start reverse This would be considered 2 wire control with either a contact used on the start FWD or start REV commands When contacts open the...

Page 34: ...start on start signal 1 ID1801 Start Signal DigIN 1 24 V DIN1 1 DIN2 2 CMA 5 GND 12 ID143 Start Stop Logic St art Forward ID1803 Start Signal 2 DigIN 2 ID143 Start Stop Logic Start Reverse 14 3 Three...

Page 35: ...Run enable when closed the drive will allow a start command and be in the ready state 9 Preset speed B0 the seven preset speeds are selected via three binary inputs this is least significant bit in t...

Page 36: ...n closed the drive will force the reference source to PI controller output 23 PI setpoint select when open parameter setpoint 1 is active when closed setpoint 2 is active 24 Motor interlock 1 when clo...

Page 37: ...n CN5 terminals 13 of the DM1 DM1 Pro it will require DIP switches SW2 2 and 3 on to complete the current loop When doing a current loop with an external supply the DIP switches SW2 2 off and 3 on P2...

Page 38: ...Reverse drive is outputting reverse phase rotation 7 At speed output frequency has reached the set reference 8 Zero frequency drive output is at zero frequency 24 STO fault output safe torque off inpu...

Page 39: ...Hold last 1 Local control or 2 Remote control Description Selects what control place the drive will start at after power is applied The default setting will hold the last state that the drive was in w...

Page 40: ...Basic settings P5 1 1ab Motor control mode ID 287 Minimum value N A Maximum value N A Default value 0 Options 0 Frequency control Output frequency is controlled directly by the frequency reference 1 S...

Page 41: ...Default Nominal Voltage of the Motor Field Weakening Point Default Nominal Frequency of the Motor 0 Linear and 1 Squared P5 1 10b Switching frequency ID 288 Minimum value MinSwitchFreq kHz Maximum val...

Page 42: ...or not the drive s nominal output current The motor s nominal current is the current that the motor can withstand in direct on line use without being overheated If you change the parameter nominal cur...

Page 43: ...Fault or 3 Warning preset frequency P6 2 13 Description This parameter defines the function of the PI feedback analog input loss response If the AI feedback is lost based off the programed AI feedback...

Page 44: ...Table 15 PI Controller Cont P7 1 Basic settings P7 1 1b PI control gain ID 1294 Minimum value 0 00 Maximum value 200 00 Default value 100 00 Description Defines the gain of the PI Controller It adjus...

Page 45: ...7 1 4b PI process unit minimum ID 1298 Minimum value 99999 99 varies Maximum value PI Process Unit Max Default value 0 00 varies Description Defines the minimum process unit value P7 1 5b PI process u...

Page 46: ...e setpoint value the drive uses This can either be an internal preset value keypad setpoint analog signal or fieldbus message P7 2 2 2a PI setpoint 1 sleep enable ID 1315 Minimum value N A Maximum val...

Page 47: ...D 1843 Minimum value 0 s Maximum value 3 600 s Default value 300 s Description Defines the maximum time for sleep over cycle checking a Parameter value can only be changed after the drive has stopped...

Page 48: ...e N A Maximum value N A Default value 0 Options 0 Only in fieldbus control mode When fieldbus is the control place and fieldbus fault is active the drive will fault on loss of communications if not in...

Page 49: ...BACnet MSTP communication P11 3 8 MSTP maximum master ID 1537 Minimum value 1 Maximum value 127 Default value 127 Description Defines the maximum number of masters that can establish connections with...

Page 50: ...ieldbus 2 Mixed interface 4 NET local on fault or 5 Dual mode Description PNU928 which specifies the control priority of the device for cyclic communication P11 5 3 Fault situation counter ID 2632 Min...

Page 51: ...Maximum value N A Default value N A Description Reads the current active IP address P12 1 3 Active subnet mask ID 1509 Minimum value N A Maximum value N A Default value N A Description Reads the curr...

Page 52: ...efault value 5 Description Maximum number of connections allowed to the drive P12 3 3 Modbus TCP unit identifier number ID 610 Minimum value N A Maximum value N A Default value 1 Description Unit iden...

Page 53: ...ication is lost fieldbus fault response will occur Description Defines the fieldbus fault condition for ethernet IP communication P12 5 BACnet IP DM1 PRO only P12 5 1a BACnet IP UDP port number ID 173...

Page 54: ...ace and Fieldbus fault is active the drive will fault on loss of communications If not in fieldbus control place will not fault 1 In all control modes no matter the control place setting If communicat...

Page 55: ...N A Options 0 Standard 1 Pump 2 Fan or 3 Multi purpose Description This parameter sets the active application if multiple applications have been loaded P13 1 3a Parameter sets ID 619 Minimum value N...

Page 56: ...r value to 0 P13 1 8 Keypad parameter lock for remote keypad only ID 625 Minimum value N A Maximum value N A Default value 0 Options 0 Change enable or 1 Change disable Description This function allow...

Page 57: ...mum value N A Maximum value N A Default value N A Description MCU application software version P13 4 4 Software bundle version ID 1714 Minimum value N A Maximum value N A Default value N A Description...

Page 58: ...ion provides features specific for HVAC applications and fan related protective features Fan application includes functions Damper control Fire mode Smoke purge and Broken belt protection I O controls...

Page 59: ...ive 5 CMA DI1 to DI4 common Grounded Allows for sourced input 6 A RS 485 signal A Fieldbus communication Modbus RTU BACNet 7 B RS 485 signal B Fieldbus communication Modbus RTU BACNet 8 AI1 Analog inp...

Page 60: ...og input 1 ground Analog input 1 common ground 10 GND I O signal ground I O ground for reference and control 11 AO1 Analog output 1 Output frequency Shows output frequency to motor 0 60 Hz 4 mA to 20...

Page 61: ...iption Output frequency Hz M1 2 Frequency reference ID 24 Minimum value Hz Maximum value Hz Default value Hz Description Reference frequency Hz M1 3 Motor speed ID 2 Minimum value rpm Maximum value rp...

Page 62: ...or Amps selectable with dipswitch M2 2 Keypad pot voltage ID 1858 Minimum value V Maximum value V Default value V Description Keypad potentiometer measured value Vdc DM1 PRO only M2 3 Analog output I...

Page 63: ...Default value 0 00 Hz Description Defines the lowest frequency at which the drive will operate This setting will limit other frequency parameter settings 1 Fire mode minimum frequency 2 Derag 3 MPFC...

Page 64: ...ue 400 00 Hz Default value MotorNomFreqMFG Hz Description Motor nameplate rated frequency This value is found on the rating plate of the motor P1 11b Local control place ID 1695 Minimum value N A Maxi...

Page 65: ...Value With Reference Scaling Reference Scaling With Reference Scaling No scaling used AI Reference Scale Minimum Value 0 AI Reference Scale Minimum Value P2 1 3ab IO terminal Start Stop logic ID 143 M...

Page 66: ...rward DIN1 and start reverse DIN2 signals are active simultaneously the start forward signal DIN1 has priority 1 P3 2 IO terminal start signal 1 start forward P3 3 IO terminal start signal 2 start rev...

Page 67: ...Stop Logic St art Forward ID1803 Start Signal 2 DigIN 2 ID143 Start Stop Logic Start Reverse 14 3 Three wire connection pulse control P3 2 IO terminal start signal 1 start forward P3 3 IO terminal sta...

Page 68: ...the rate defined by motor pot ramp time 14 Decel pot value when closed the motor potentiometer value will decrement at the rate defined by motor pot ramp time 15 Reset pot zero when closed the motor...

Page 69: ...ler output 23 PI setpoint select when open parameter setpoint 1 is active When closed setpoint 2 is active 24 Motor interlock 1 when closed the motor will be enabled to run 25 Smoke mode when closed s...

Page 70: ...ntrol when closed the drive will be forced to the remote control place 20 Local control when closed the drive will be forced to the Local control place 21 Parameter 1 2 sel when open parameter set 1 i...

Page 71: ...lt value 1 Options 0 0 20 mA or 1 0 10 V Description Defines the analog input mode to current or voltage the DIP switches on control board will need to be set to the same mode as this parameter DM1 CN...

Page 72: ...V Description With this parameter you can select the analog input 1 signal range For selection Customized see AI Custom Min and AI Custom Max this enables a customized signal range Output Frequency AI...

Page 73: ...olt regular over volt regulator is enabled 20 Under volt regular under volt regulator is enabled 21 4 mA fault 4 mA fault has occurred 22 External fault external fault has occurred 23 Motor thermal fa...

Page 74: ...fault 4 mA fault has occurred 22 External fault external fault has occurred 23 Motor thermal fault motor thermal fault has occurred 24 STO fault output safe torque Off input is activated 25 Control f...

Page 75: ...us process data input 8 0 100 22 User defined output user defined minimum user defined maximum 23 Motor torque 0 200 or 24 Motor power absolute value 0 100 Description Select the function desired to t...

Page 76: ...om maximum frequency The drive will catch a spinning motor This setting searches for the current frequency using the maximum operating frequency as a starting point Description Selects the start mode...

Page 77: ...selected with the programmable digital input P4 1 13b Decel time 2 ID 250 Minimum value 0 1 s Maximum value 3000 0 s Default value 10 0 s Description These values correspond to the time required for t...

Page 78: ...the speed 3 Linear with flux optimization the drive starts to search for the minimum motor current in order to save energy This mode is called Eaton s Active Energy Control which will reduce the volta...

Page 79: ...nt of the motor not the drive s nominal output current The motor s nominal current is the current that the motor can withstand in direct on line use without being overheated If you change the paramete...

Page 80: ...n 1 Warning 2 Fault or 3 Warning preset frequency P6 2 13 Description This parameter defines the function of the PI feedback analog input loss response If the AI feedback is lost based off the program...

Page 81: ...macros Table 29 PI Controller Cont P7 1 Basic settings P7 1 1b PI control itime ID 1294 Minimum value 0 00 Maximum value 200 00 Default value 100 00 Description Defines the gain of the PI Controller...

Page 82: ...HG 43 ft 44 m Description Defines the unit type for PI feedback unit P7 1 4b PI process unit minimum ID 1298 Minimum value 99999 99 varies Maximum value PID1_ProcessUnitMax varies Default value 0 00 v...

Page 83: ...andard P7 2 1 1b PI keypad setpoint 1 ID 1307 Minimum value PI Process Unit Min Maximum value PI Process Unit Max Default value 0 00 varies Description Keypad PI reference value setpoint 1 P7 2 1 2b P...

Page 84: ...2 2 6b PI setpoint 1 sleep level ID 2450 Minimum value Min Freq Maximum value Max Freq Default value 0 00 Hz Description Defines the level of which the unit value is used to look at to go into the sle...

Page 85: ...oost ID 1329 Minimum value 2 00 varies Maximum value 2 00 varies Default value 1 00 varies Description The setpoint can be boosted via a multiplier value P7 2 3 6b PI setpoint 2 sleep level ID 2452 Mi...

Page 86: ...ault when changing macros Table 32 HVAC parameters Cont P8 1 Damper DM1 PRO P8 1 1ab Damper start ID 483 Minimum value N A Maximum value N A Default value 0 Options 0 Normal 1 Damper start 2 Damper to...

Page 87: ...t value 100 00 Description This parameter sets the drive operating percentage based off the 0 being minimum frequency P1 1 and 100 being maximum frequency P1 2 for fire mode reference 2 P8 2 6 Fire mo...

Page 88: ...s the value for the minimum torque allowed at zero frequency If you change the value of P1 6 nominal motor current this parameter is automatically restored to the default value P8 3 4b Broken belt tim...

Page 89: ...TU protocol status ID 588 Minimum value N A Maximum value N A Default value N A Options 0 Initial 1 Stopped 2 Operational or 3 Faulted Description This parameter shows the protocol status for RS 485 c...

Page 90: ...protocol status for BACnet MSTP communication P11 3 7 MSTP fault response ID 2526 Minimum value N A Maximum value N A Default value 0 Options 0 Only in fieldbus control mode when fieldbus is the cont...

Page 91: ...1 Pro P11 5 1 Parameter access ID 2630 Minimum value N A Maximum value N A Default value 1 Options 0 No permission to read write on acyclic channel 1 Acyclic read write are allowed on Profibus Descrip...

Page 92: ...eset Description Bluetooth pairing reset a Parameter value can only be changed after the drive has stopped b Parameter value will be set to be default when changing macros Table 34 Ethernet communicat...

Page 93: ...mmunication fault occurs over ethernet P12 2 Trusted IP filter DM1 PRO only P12 2 1 Trusted IP white list ID 68 Minimum value N A Maximum value N A Default value 192 168 1 255 Description Defines the...

Page 94: ...setting if communication is lost fieldbus fault response will occur Description Defines the fieldbus fault condition for modbus TCP communication P12 4 Ethernet IP DM1 PRO only P12 4 1a Ethernet base...

Page 95: ...Enables BACNET IP foreign device configuration P12 5 3a BACnet IP BBMD IP ID 1735 Minimum value N A Maximum value N A Default value 0 0 0 0 Description Displays the BACnet BBMD IP address P12 5 4a BAC...

Page 96: ...nstance number P12 6 Web UI DM1 PRO only P12 6 1 Web UI protocol status ID 2915 Minimum value N A Maximum value N A Default value N A Options 0 Off 1 Operational or 2 Faulted Description This paramete...

Page 97: ...parameter groups to the keypad P13 1 5a Down from keypad for remote keypad only ID 621 Minimum value N A Maximum value N A Default value N A Options 0 No 1 All parameters 2 All no motor or 3 Applicat...

Page 98: ...this parameter is set to Disabled The Start up Wizard is always enabled for the initial power up of the DM1 PRO By setting this parameter to Disable without going through the Start up Wizard it will...

Page 99: ...eypad only ID 627 Minimum value N A Maximum value N A Default value 0 Options 0 Change enable or 1 Change disable Description The keypad display can display three actual monitored values at the same t...

Page 100: ...ump related protective features Pump application includes functions Pump derag mode Valve control Backspin control Minimum run time Separate minimum frequency ramp time Multi pump control Pipe fill mo...

Page 101: ...to DI4 common Grounded Allows for sourced input 6 A RS 485 signal A Fieldbus communication Modbus RTU BACNet 7 B RS 485 signal B Fieldbus communication Modbus RTU BACNet 8 AI1 Analog input 1 0 10 V V...

Page 102: ...log input 1 ground Analog input 1 common ground 10 GND I O signal ground I O ground for reference and control 11 AO1 Analog output 1 Output frequency Shows output frequency to motor 0 60 Hz 4 mA to 20...

Page 103: ...ription Output frequency Hz M1 2 Frequency reference ID 24 Minimum value Hz Maximum value Hz Default value Hz Description Reference frequency Hz M1 3 Motor speed ID 2 Minimum value rpm Maximum value r...

Page 104: ...or Amps selectable with dipswitch M2 2 Keypad pot voltage ID 1858 Minimum value V Maximum value V Default value V Description Keypad potentiometer measured value Vdc DM1 PRO only M2 3 Analog output I...

Page 105: ...ng mode of drive 1 while using multi pump mode M7 1 2 Drive 2 ID 2230 Minimum value N A Maximum value N A Default value N A Options 0 Offline 1 Slave drive or 2 Master drive Description Provides the o...

Page 106: ...N A Default value 5 Options 0 Stopped 1 Sleep 2 Regulating 3 Wait for CMD 4 Following or 5 Unknown Description Provides the run status of drive 3 while using the multi pump mode M7 2 4 Drive 4 ID 2255...

Page 107: ...3 5 Drive 5 ID 2268 Minimum value N A Maximum value N A Default value N A Options 0 Disconnected 1 Fault 2 Pump lost 3 Need alternation or 4 No error Description Provides the network status of drive...

Page 108: ...nimum value V Maximum value V Default value V Description Provides the motor voltage Vac of drive 1 while using the multi pump mode M8 3 2 Drive 2 ID 2235 Minimum value V Maximum value V Default value...

Page 109: ...imum value Default value Description Provides the motor torque of drive 4 while using the multi pump mode M8 5 5 Drive 5 ID 2273 Minimum value Maximum value Default value Description Provides the moto...

Page 110: ...of drive 1 while using the multi pump mode M8 8 2 Drive 2 ID 2240 Minimum value Hours Maximum value Hours Default value Hours Description Provides the motor run time h of drive 2 while using the multi...

Page 111: ...limit P1 3b Accel time 1 ID 103 Minimum value 0 1 s Maximum value 3 000 0 s Default value 20 0 s Description Defines the time required for the output frequency to accelerate from zero frequency to max...

Page 112: ...ault value 1 Options 0 AI 1 drive ref pot 4 maximum frequency 6 keypad or 7 fieldbus ref Description Defines the signal location for the speed reference in local mode P1 13b Remote control place ID 13...

Page 113: ...alue With Reference Scaling Reference Scaling With Reference Scaling No scaling used AI Reference Scale Minimum Value 0 AI Reference Scale Minimum Value P2 1 3ab IO terminal Start Stop logic ID 143 Mi...

Page 114: ...orward DIN1 and start reverse DIN2 signals are active simultaneously the start forward signal DIN1 has priority 1 P3 2 IO terminal start signal 1 start forward P3 3 IO terminal start signal 2 start re...

Page 115: ...Stop Logic St art Forward ID1803 Start Signal 2 DigIN 2 ID143 Start Stop Logic Start Reverse 14 3 Three wire connection pulse control P3 2 IO terminal start signal 1 start forward P3 3 IO terminal st...

Page 116: ...e defined by motor pot ramp time 14 Decel pot value when closed the motor potentiometer value will decrement at the rate defined by motor pot ramp time 15 Reset pot zero when closed the motor potentio...

Page 117: ...by motor pot ramp time 14 Decel pot value when closed the motor potentiometer value will decrement at the rate defined by motor pot ramp time 15 Reset pot zero when closed the motor potentiometer val...

Page 118: ...by motor pot ramp time 14 Decel pot value when closed the motor potentiometer value will decrement at the rate defined by motor pot ramp time 15 Reset pot zero when closed the motor potentiometer val...

Page 119: ...ontrol when closed the drive will be forced to the remote control place 20 Local control when closed the drive will be forced to the Local control place 21 Parameter 1 2 sel when open parameter set 1...

Page 120: ...ult value 1 Options 0 0 20 mA or 1 0 10 V Description Defines the analog input mode to current or voltage the DIP switches on control board will need to be set to the same mode as this parameter DM1 C...

Page 121: ...V Description With this parameter you can select the analog input 1 signal range For selection Customized see AI Custom Min and AI Custom Max this enables a customized signal range Output Frequency A...

Page 122: ...volt regular over volt regulator is enabled 20 Under volt regular under volt regulator is enabled 21 4 mA fault 4 mA fault has occurred 22 External fault external fault has occurred 23 Motor thermal f...

Page 123: ...A fault 4 mA fault has occurred 22 External fault external fault has occurred 23 Motor thermal fault motor thermal fault has occurred 24 STO fault output safe torque Off input is activated 25 Control...

Page 124: ...bus process data input 8 0 100 22 User defined output user defined minimum user defined maximum 23 Motor torque 0 200 or 24 Motor power absolute value 0 100 Description Select the function desired to...

Page 125: ...rom maximum frequency The drive will catch a spinning motor This setting searches for the current frequency using the maximum operating frequency as a starting point Description Selects the start mode...

Page 126: ...value 0 1 s Maximum value 3000 0 s Default value 10 0 s Description These values correspond to the time required for the output frequency to decelerate from the set maximum frequency to the zero frequ...

Page 127: ...the speed 3 Linear with flux optimization the drive starts to search for the minimum motor current in order to save energy This mode is called Eaton s Active Energy Control which will reduce the volt...

Page 128: ...f the motor not the drive s nominal output current The motor s nominal current is the current that the motor can withstand in direct on line use without being overheated If you change the parameter no...

Page 129: ...Warning 2 Fault or 3 Warning preset frequency P6 2 13 Description This parameter defines the function of the PI feedback analog input loss response If the AI feedback is lost based off the programed A...

Page 130: ...g macros Table 46 PI Controller Cont P7 1 Basic settings P7 1 1b PI control gain ID 1294 Minimum value 0 00 Maximum value 200 00 Default value 100 00 Description Defines the gain of the PI Controller...

Page 131: ...Default value 0 00 varies Description Defines the minimum process unit value P7 1 5b PI process unit maximum ID 1300 Minimum value PI Process Unit Min Maximum value 99999 99 varies Default value 100 0...

Page 132: ...ypad PI reference value setpoint 2 P7 2 1 3b PI wake up action ID 2466 Minimum value N A Maximum value N A Default value 0 Options 0 Wake up when below wake up level 1 Wake up when above wake up level...

Page 133: ...o the sleep mode P7 2 2 7b SP1 sleep mode over cycle time ID 1842 Minimum value 0 00 varies Maximum value 10 00 varies Default value 0 00 varies Description Defines the count the drive come in and out...

Page 134: ...level for the sleep delay time it will put the drive into the sleep mode P7 2 3 7b SP2 sleep mode over cycle time ID 1844 Minimum value 0 00 varies Maximum value 10 00 varies Default value 0 00 varies...

Page 135: ...tion will become activated start stop both or based off the digital input P9 1 3b Deragging run time ID 2470 Minimum value 1 00 s Maximum value 3 600 00 s Default value 0 00 s Description Defines the...

Page 136: ...P9 3 1ab Multi pump mode ID 2279 Minimum value N A Maximum value N A Default value 0 Options 0 Disabled or 1 Multi drive network Description Determines the number of drives being used in the multi pum...

Page 137: ...multi drive system lost the master The slave drive can continue run if it set to be Automatic However the slave drive will stop immediately if it is set to be Stop P9 3 11b Add remove drive selection...

Page 138: ...0 00 varies Default value 0 00 varies Description If the monitor value is less than low level value and the output frequency is more than low frequency check the pipe fill loss start P9 4 4ab Pipe fil...

Page 139: ...ime P9 5 6b Prime pump level 2 ID 2434 Minimum value 0 00 varies Maximum value 6 000 00 varies Default value 0 00 varies Description This defines the level at which the pre charge function will drop o...

Page 140: ...1a Slave address ID 587 Minimum value 1 00 varies Maximum value 247 00 varies Default value 1 00 varies Description This parameter defines the slave address for RS 485 communication P11 2 2a Baud rate...

Page 141: ...ber of the drive on the BACnet MSTP network P11 3 4 MSTP communication timeout ID 598 Minimum value 0 ms Maximum value 60 000 ms Default value 10 000 ms Description Selects the time to wait before a c...

Page 142: ...A Default value 0 Options 0 Only in fieldbus control mode when fieldbus is the control place and fieldbus fault is active The drive will fault on loss of communications If not in fieldbus control plac...

Page 143: ...the protocol status for SWD card P11 6 Bluetooth P11 6 1 Bluetooth enabled ID 1895 Minimum value N A Maximum value N A Default value 0 Options 0 Disabled or 1 Enabled Description Bluetooth enabled P11...

Page 144: ...1505 Minimum value N A Maximum value N A Default value 192 168 1 1 Description Defines the static default gateway P12 1 9 Ethernet communication timeout ID 611 Minimum value 0 ms Maximum value 60 000...

Page 145: ...place setting if communication is lost fieldbus fault response will occur Description Defines the fieldbus fault condition for modbus TCP communication P12 4 Ethernet IP DM1 PRO only P12 4 1a Ethernet...

Page 146: ...n Enables BACNET IP foreign device configuration P12 5 3a BACnet IP BBMD IP ID 1735 Minimum value N A Maximum value N A Default value 0 0 0 0 Description Displays the BACnet BBMD IP address P12 5 4a B...

Page 147: ...net instance number P12 6 Web UI DM1 PRO only P12 6 1 Web UI protocol status ID 2915 Minimum value N A Maximum value N A Default value N A Options 0 Off 1 Operational or 2 Faulted Description This par...

Page 148: ...g parameter groups to the keypad P13 1 5a Down from keypad for remote keypad only ID 621 Minimum value N A Maximum value N A Default value N A Options 0 No 1 All parameters 2 All no motor or 3 Applica...

Page 149: ...d this parameter is set to Disabled The Start up Wizard is always enabled for the initial power up of the DM1 PRO By setting this parameter to Disable without going through the Start up Wizard it will...

Page 150: ...keypad only ID 627 Minimum value N A Maximum value N A Default value 0 Options 0 Change enable or 1 Change disable Description The keypad display can display three actual monitored values at the same...

Page 151: ...ell as torque control For tuning the V Hz curve it has the ability to go out and ID the motor characteristic and enters those specific measurements into its parameters for better control Drive motor p...

Page 152: ...the drive 5 CMA DI1 to DI4 common Grounded Allows for sourced input 6 A RS 485 signal A Fieldbus communication Modbus RTU BACNet 7 B RS 485 signal B Fieldbus communication Modbus RTU BACNet 8 AI1 Ana...

Page 153: ...I1 Analog input 1 ground Analog input 1 common ground 10 GND I O signal ground I O ground for reference and control 11 AO1 Analog output 1 Output frequency Shows output frequency to motor 0 60 Hz 4 mA...

Page 154: ...erlock 3 Interlock 2 Interlock 1 On Off On Off On Off On Off On Off On Off On Off On Off Max Frequency Aux 3 Running Aux 2 Running Aux 1 Running Main Drive Running Min Frequency f t Aux 1 2 and 3 Star...

Page 155: ...145 Chapter 7 Multi purpose application POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN September 2021 www eaton com Figure 10 Multi pump control curve Figure 11 Multi drive multi pump layout...

Page 156: ...5 Feedback out of bandwidth output frequency below de staging frequency start delay counter delay times out remove aux 2 motor first because it s the last one which been added 6 As above remove aux 3...

Page 157: ...ID 24 Minimum value Hz Maximum value Hz Default value Hz Description Reference frequency Hz M1 3 Motor speed ID 2 Minimum value rpm Maximum value rpm Default value rpm Description Motor output speed...

Page 158: ...er measured value Vdc DM1 PRO only M2 3 Analog output ID 25 Minimum value Varies Maximum value Varies Default value Varies Description Analog output 1 measured value Vdc or Amps selectable with parame...

Page 159: ...indicator Bit 11 MC_DC_Brake Bit 12 Run enable Bit 13 Run bypass Bit 14 External brake control or Bit 15 In bypass mode Description Application status word will provide additional status indication of...

Page 160: ...e Default value Description PI output M5 5 PI status ID 23 Minimum value N A Maximum value N A Default value N A Options 0 Stopped 1 Running or 2 Sleep mode Description PI status indication indicates...

Page 161: ...ue N A Options 0 Offline 1 Slave drive 2 Master drive or 3 Redundant drive Description Provides the operating mode of drive 4 while using multi pump mode M7 1 5 Drive 5 ID 2266 Minimum value N A Maxim...

Page 162: ...5 Options 0 Stopped 1 Sleep 2 Regulating 3 Wait for CMD 4 Following or 5 Unknown Description Provides the run status of drive 5 while using the multi pump mode M7 3 Network status DM1 Pro M7 3 1 Drive...

Page 163: ...alue Maximum value Default value Description Provides the latest fault code of drive 2 while using the multi pump mode M8 1 3 Drive 3 ID 2245 Minimum value Maximum value Default value Description Prov...

Page 164: ...hile using the multi pump mode M8 3 4 Drive 4 ID 2259 Minimum value V Maximum value V Default value V Description Provides the motor voltage Vac of drive 4 while using the multi pump mode M8 3 5 Drive...

Page 165: ...mum value Default value Description Provides the motor power of drive 1 while using the multi pump mode M8 6 2 Drive 2 ID 2238 Minimum value Maximum value Default value Description Provides the motor...

Page 166: ...pump mode M8 8 4 Drive 4 ID 2264 Minimum value Hours Maximum value Hours Default value Hours Description Provides the motor run time h of drive 4 while using the multi pump mode M8 8 5 Drive 5 ID 2276...

Page 167: ...equired for the output frequency to decelerate from maximum frequency to zero frequency P1 5b Motor type selection ID 1820 Minimum value N A Maximum value N A Default value 0 Options 0 Inverter duty 1...

Page 168: ...135 Minimum value N A Maximum value N A Default value 0 Options 0 IO terminal 1 fieldbus or 3 keypad Description Defines the signal location for the start command in remote mode I O terminals would b...

Page 169: ...1 to run forward and a maintained signal on start signal 2 to enable the drive to run 3 Start pulse stop pulse used for three wire operation start signal 1 uses a normally open start and start signal...

Page 170: ...orward DIN1 and start reverse DIN2 signals are active simultaneously the start forward signal DIN1 has priority 1 P3 2 IO terminal start signal 1 start forward P3 3 IO terminal start signal 2 start re...

Page 171: ...ard ID1803 Start Signal 2 DigIN 2 ID143 Start Stop Logic Start Reverse 14 3 Three wire connection pulse control P3 2 IO terminal start signal 1 start forward P3 3 IO terminal start signal 2 start reve...

Page 172: ...viewable using a remote keypad PowerXpert inControl or the built in webserver P2 1 6b External fault 3 text ID 2299 Minimum value N A Maximum value N A Default value 2 Options 0 External fault 1 Vibr...

Page 173: ...decrement at the rate defined by motor pot ramp time 15 Reset pot zero when closed the motor potentiometer value will reset to zero 16 Accel Decel time set when open Accel Decel time 1 will be used W...

Page 174: ...crement at the rate defined by motor pot ramp time 15 Reset pot zero when closed the motor potentiometer value will reset to zero 16 Accel decel time set when open accel decel time 1 will be used When...

Page 175: ...crement at the rate defined by motor pot ramp time 15 Reset pot zero when closed the motor potentiometer value will reset to zero 16 Accel decel time set when open accel decel time 1 will be used When...

Page 176: ...crement at the rate defined by motor pot ramp time 15 Reset pot zero when closed the motor potentiometer value will reset to zero 16 Accel decel time set when open accel decel time 1 will be used When...

Page 177: ...rate defined by motor pot ramp time 15 Reset pot zero when closed the motor potentiometer value will reset to zero 16 Accel decel time set when open accel decel time 1 will be used When closed accel...

Page 178: ...am when closed no changes can be made to any setting in the drive 19 Remote control when closed the drive will be forced to the remote control place 20 Local control when closed the drive will be forc...

Page 179: ...z Maximum value MaxFreq Hz Default value 0 00 Hz Description Defines the jogging speed set point this speed is selected with the digital input programmed for jogging speed When enabled the drive start...

Page 180: ...ue AI1 Signal Range 1 AI1 Custom Max P2 4 3b AI custom minimum ID 176 Minimum value 0 00 Maximum value Ai1CustomMax Default value 0 00 Descriptions Defines the minimum percentage for the input range t...

Page 181: ...cy AI Reference Scale Maximum Value 0 100 AI1 Term 2 AI1 Custom Maximum AI1 Custom Minimum AI Signal Range 0 AI1 0 100 AI Signal Range 1 AI1 Custom AI Reference Scale Minimum Value Output Frequency AI...

Page 182: ...minimum percentage for the input range to be associated with AI reference minimum scale P2 5 2b Pot custom maximim ID 1815 Minimum value 0 00 Maximum value 100 00 Default value 100 00 Description Defi...

Page 183: ...fault has occurred 23 Motor thermal fault motor thermal fault has occurred 24 STO fault output safe torque Off input is activated 25 Control from IO I O is the selected start command location 26 Remot...

Page 184: ...safe torque Off input is activated 25 Control from IO I O is the selected start command location 26 Remote control remote is the control place 27 Un requested rotation direction the active direction...

Page 185: ...er volt regular over volt regulator is enabled 20 Under volt regular under volt regulator is enabled 21 4 mA fault 4 mA fault has occurred 22 External fault external fault has occurred 23 Motor therma...

Page 186: ...fault output safe torque off input is activated 25 Control from IO I O is the selected start command location 26 Remote control remote is the control place 27 Unrequested rotation direction the activ...

Page 187: ...le DO 2 Warning W S enable DO or 3 Fault enable DO Description Supervision display selection P3 2 7b Torque limit supervision value ID 160 Minimum value 1 000 00 Maximum value 1 000 00 Default value 1...

Page 188: ...re limit supervision value ID 166 Minimum value 10 0 C Maximum value 75 0 C Default value 40 0 C Description Selects the drive temperature value supervised by the drive temperature limit supervision f...

Page 189: ...ervised by the analog reference limit supervision function P3 2 25b AI supervision hysteresis ID 2198 Minimum value 1 00 Maximum value 10 00 Default value 1 00 Description This value selects the bandw...

Page 190: ...S enable DO 2 Warning W S enable DO or 3 Fault enable DO Description Supervision display selection P3 2 32b PI supervision upper limit ID 1347 Minimum value PI Process Unit Min varies Maximum value PI...

Page 191: ...8 0 100 22 User defined output user defined minimum user defined maximum 23 Motor torque 0 200 or 24 Motor power absolute value 0 100 Description Select the function desired to the terminal AO1 P3 3...

Page 192: ...ard the rotation of the motor is forward or clockwise direction when the keypad is the active control place Reverse the rotation of the motor is reversed or counter clockwise direction when the keypad...

Page 193: ...n P4 1 9b Stop mode ID 253 Minimum value N A Maximum value N A Default value 1 Options 0 Coasting After a stop command the motor coasts to a stop uncontrolled by the drive 1 Ramp After the stop comman...

Page 194: ...or the output frequency to decelerate from the set maximum frequency to the zero frequency These parameters provide the possibility to set two different acceleration deceleration time sets for one app...

Page 195: ...iven or before ramping to reference level This is to stop motors that are potentially spinning before a run command is given P4 2 4ab Stop DC brake frequency ID 262 Minimum value 0 10 Hz Maximum value...

Page 196: ...its The ramping speed selected acceleration deceleration time 1 or 2 is multiplied with this factor e g value 0 1 makes the acceleration time 10 times shorter than outside the prohibit frequency range...

Page 197: ...time 10 times shorter than outside the prohibit frequency range limits P4 4 Energy savings calculations P4 4 1b Currency ID 2122 Minimum value N A Maximum value N A Default value 0 Options 0 1 2 3 4 R...

Page 198: ...igh loads P5 1 4ab V Hz ratio ID 108 Minimum value N A Maximum value N A Default value 0 Options 0 Linear the voltage of the motor changes linearly with the frequency in the constant flux area from 0...

Page 199: ...switching frequency for the PWM output waveform P5 1 11b Sine filter enabled ID 1665 Minimum value N A Maximum value N A Default value 0 Options 0 Disabled or 1 Enabled Description This parameter ena...

Page 200: ...etic inductance that does not link to a winding in the motor The value is measured when performing identification P5 1 20a Mutual inductance ID 774 Minimum value 0 10 mh Maximum value 6553 50 mh Defau...

Page 201: ...mode when in frequency region 1 for faster speed response P5 2 3 Speed control Ti1 ID 1831 Minimum value 1 ms Maximum value 3 000 ms Default value 100 ms Description Sets time constant of Vector cont...

Page 202: ...Options 0 Align 1 Six pluse or 2 HFI Description PM initial angle detect method P5 2 16a PM initial time ID 1891 Minimum value 0 0 s Maximum value 60 0 s Default value 0 7 s Description PM initial ang...

Page 203: ...ing 2 Fault stop mode after fault according to parameter stop mode or 3 Fault stop mode after fault always by coasting Description If a fault condition is selected the drive will stop and activate the...

Page 204: ...a greater value than InMotor 2 If P1 6 nominal motor current is changed this parameter is automatically restored to the default value IL P6 1 8b Stall time limit ID 315 Minimum value 1 0 s Maximum va...

Page 205: ...he parameter to 0 will reset the underload time counter to zero P6 1 11ab Underload Fnom torque ID 318 Minimum value 10 0 Maximum value 150 0 Default value 50 0 Description The torque limit can be set...

Page 206: ...ng read from the drive will turn on the output to allow current to flow to the motor this is typically used when the motor is not running P6 1 15b Preheat control source ID 2160 Minimum value N A Maxi...

Page 207: ...value N A Default value 0 Options 0 No response 1 Warning 2 Warning he frequency from 10 seconds back is set as reference 3 Warning the preset frequency P6 2 4 is set as reference 4 Fault stop mode af...

Page 208: ...cate warning if STO clears drive will run without reset 2 Fault drive will indicate fault require reset to start again Description STO fault response defines the function of how the STO input will be...

Page 209: ...value 2 Options 0 No action 1 Warning 2 Fault or 3 Fault coast Description This sets the response mode for the fieldbus fault when a fieldbus mode is used and communication is lost between the PLC an...

Page 210: ...mum value N A Default value 0 Options 0 Flying start from stop frequency 1 Start according to parameter stop mode or 2 Flying start from maximum frequency Description The start function for automatic...

Page 211: ...This parameter determines how many automatic restarts can be made during the trial time 0 No automatic restart after external fault trip 0 Number of automatic restarts after external fault trip P6 4 1...

Page 212: ...HG 43 ft or 44 m Description Defines the unit type for PI feedback unit P7 1 4b PI process unit minimum ID 1298 Minimum value 99999 99 varies Maximum value PI Process Unit Max varies Default value 0 0...

Page 213: ...Standard P7 2 1 1b PI keypad setpoint 1 ID 1307 Minimum value PI Process Unit Min Maximum value PI Process Unit Max Default value 0 00 varies Description Keypad PI reference value setpoint 1 P7 2 1 2b...

Page 214: ...ia a multiplier value P7 2 2 6b PI setpoint 1 sleep level ID 2450 Minimum value MinFreq Hz Maximum value MaxFreq Hz Default value 0 00 Hz Description Defines the level of which the unit value is used...

Page 215: ...s based of the of feedback which can be scaled based off the PI unit min max values P7 2 3 5b PI setpoint 2 boost ID 1329 Minimum value 2 00 varies Maximum value 2 00 varies Default value 1 00 varies...

Page 216: ...P8 1 Damper DM1 PRO P8 1 1ab Damper start ID 483 Minimum value N A Maximum value N A Default value 0 Options 0 Start standard start 1 Interlocked start To use this a relay output RO1 RO2 needs to be...

Page 217: ...s parameter sets the drive operating percentage based off the 0 being minimum frequency P1 1 and 100 being maximum frequency P1 2 for fire mode reference 1 P8 2 5b Fire mode frequency reference 2 ID 5...

Page 218: ...the value for the minimum torque allowed at zero frequency If you change the value of P1 6 nominal motor current this parameter is automatically restored to the default value P8 3 4b Broken belt time...

Page 219: ...00 Hz Description Defines the frequency the drive will run at in the forward reverse direction when in the derag mode P9 1 5b Derag off delay ID 2472 Minimum value 1 s Maximum value 600 s Default val...

Page 220: ...drive active at one time By setting value to above one it allows for bringing in additional drives to maintain the sytem P9 3 3ab Drive ID ID 2278 Minimum value 0 Maximum value 5 Default value 0 Descr...

Page 221: ...led ID 2280 Minimum value N A Maximum value N A Default value 0 Options 0 Disabled or 1 Enabled Description The run time counter will start counting only if this parameter is enabled P9 3 13b Run time...

Page 222: ...y point at which the drive needs to be above to enable the loss of prime feature When set to 0 Hz protection is disabled P9 4 5b Pipe fill loss high level ID 1851 Minimum value 0 0 varies Maximum valu...

Page 223: ...ch the prime pump function will drop out If the feedback level raises above this value prime pump becomes deactivated If the level is not reached it will switch after the delay time P9 5 7b Prime pump...

Page 224: ...D 0 P10 1 2b FB process data input 2 selection ID 2534 Minimum value 0 Maximum value 12 464 Default value 2 542 Description With the fieldbus data output selections parameter monitor IDs can be assign...

Page 225: ...cess data IN4 Acceleration time 1 ID 103 Process data IN5 Deceleration time 1 ID 104 Process data IN6 Current limit ID 107 Process data IN7 NULL ID 0 or Process data IN8 NULL ID 0 P10 1 6b FB process...

Page 226: ...tor torque ID 4 Process data Out5 Motor power ID 5 Process data Out6 Motor voltage ID 6 Process data Out7 DC link voltage ID 7 or Process data Out8 Latest fault code ID 28 P10 2 2b FB process data out...

Page 227: ...Out4 Motor torque ID 4 Process data Out5 Motor power ID 5 Process data Out6 Motor voltage ID 6 Process data Out7 DC link voltage ID 7 or Process data Out8 Latest fault code ID 28 P10 2 6b FB process d...

Page 228: ...value N A Maximum value N A Default value 1 Options 0 Not used 1 Ready 2 Run 3 Fault 4 Fault invert 5 Warning 6 Reversed 7 At speed 8 Zero frequency 9 Frequency limit supervision 10 PI supervision 11...

Page 229: ...ver heat fault 18 Overcurrent regular 19 Overvoltage regular 20 Undervoltage regular 21 4 mA reference fault warning 22 External fault warning 23 Motor thermal protection 24 STO fault output 25 Contro...

Page 230: ...ver heat fault 18 Overcurrent regular 19 Overvoltage regular 20 Undervoltage regular 21 4 mA reference fault warning 22 External fault warning 23 Motor thermal protection 24 STO fault output 25 Contro...

Page 231: ...ver heat fault 18 Overcurrent regular 19 Overvoltage regular 20 Undervoltage regular 21 4 mA reference fault warning 22 External fault warning 23 Motor thermal protection 24 STO fault output 25 Contro...

Page 232: ...ver heat fault 18 Overcurrent regular 19 Overvoltage regular 20 Undervoltage regular 21 4 mA reference fault warning 22 External fault warning 23 Motor thermal protection 24 STO fault output 25 Contro...

Page 233: ...ver heat fault 18 Overcurrent regular 19 Overvoltage regular 20 Undervoltage regular 21 4 mA reference fault warning 22 External fault warning 23 Motor thermal protection 24 STO fault output 25 Contro...

Page 234: ...ver heat fault 18 Overcurrent regular 19 Overvoltage regular 20 Undervoltage regular 21 4 mA reference fault warning 22 External fault warning 23 Motor thermal protection 24 STO fault output 25 Contro...

Page 235: ...ol 30 Valve control 31 Jog speed select 32 Fieldbus digital input 1 33 Fieldbus digital input 2 34 DC charge switch close 35 Preheat active 36 Cold weather active 37 PI Sleep 38 2nd stage ramp frequen...

Page 236: ...inimum value N A Maximum value N A Default value 0 Options 0 Only in fieldbus control mode When fieldbus is the control place and fieldbus fault is active the drive will fault on loss of communication...

Page 237: ...mber of masters that can establish connections with the drive P11 4 SA bus DM1 Pro P11 4 1a SA bus device address ID 1726 Minimum value 204 Maximum value 254 Default value 204 Description This paramet...

Page 238: ...nter Only write of 0 is allowed then the whole fault buffer actual fault situation and all other fault situations and the fault message counter parameter 944 are erased P11 5 4 Board status ID 2609 Mi...

Page 239: ...rent active subnet mask P12 1 4 Active default gateway ID 1511 Minimum value N A Maximum value N A Default value N A Description Reads the current active default gateway P12 1 5 MAC address ID 1513 Mi...

Page 240: ...modbus TCP P12 3 4 Modbus TCP protocol status ID 612 Minimum value N A Maximum value N A Default value N A Options 0 Stopped 1 Operational or 2 Faulted Description This parameter shows the protocol s...

Page 241: ...value N A Maximum value N A Default value 47 808 Options 47808 BAC0 47809 BAC1 47810 BAC2 47811 BAC3 47812 BAC4 47813 BAC5 47814 BAC6 47815 BAC7 47816 BAC8 47817 BAC9 47818 BACA 47819 BACB 47820 BACC...

Page 242: ...communication P12 5 9a BACnet IP instance number ID 1742 Minimum value 0 Maximum value 4 194 302 Default value 0 Description Displays the BACnet instance number P12 6 Web UI DM1 PRO only P12 6 1 Web...

Page 243: ...loaded P13 1 3a Parameter sets ID 619 Minimum value N A Maximum value N A Default value N A Options 0 No 1 Load factory default parameters 2 Reload set 1 3 Reload set 2 4 Store parameter set 1 5 Stor...

Page 244: ...er value changes or password changes By default the password function is not in use If you want to activate the password change the value of this parameter to any number between 1 and 9 999 To deactiv...

Page 245: ...an receives a stop command when the heat sink temperature falls to 55 C 131 F The fan runs for about a minute after receiving the stop command or switching on the power as well as after changing the v...

Page 246: ...42 HG 43 ft 44 m 45 Hz 46 strokes min Description Allows for changing the M1 1 and M1 2 value to a desired unit that will reflect the application From there with P13 3 2 and P13 3 3 it will allow sett...

Page 247: ...me time This parameter determines if the operator is allowed to replace the values monitored with other values P13 5 3 Keypad lock PIN ID 75 Minimum value 0 Maximum value 9 999 Default value 0 Descrip...

Page 248: ...t ID 639 Minimum value N A Maximum value N A Default value 0 Options 0 Not reset 1 Clear trip MWh count or 2 Clear trip power count Description Resets the day and hour motor or drive running counter a...

Page 249: ...Over voltage Fault The DC link voltage has exceeded the limits defined Too short a deceleration time Brake chopper is disabled High overvoltage spikes in supply Start stop sequence too fast Make decel...

Page 250: ...nge Warning Power board or option card change Alarm will reset 38 Device added Warning Power board or option board added Device is ready for use Old parameter settings will be used 39 Device removed F...

Page 251: ...fieldbus reference is the remote reference OR the fieldbus control place is the remote control place and the fault protection is not NO action Check ethernet communication wiring Verify drive paramete...

Page 252: ...pe level and the drive output frequency is more than broke pipe frequency for delay time 125 Freq limit supv Freq limit No action The output frequency exceeds the range of frequency supervision limit...

Page 253: ...er Serial Number Device Name Information specific to communication protocols is available form parameter menu as below IP Address Mode Active IP Address MAC Address See application manual for these pa...

Page 254: ...when motor is in stop mode In which way to enhance the motor security The parameters are listed in the application manual 3 Through Power Xpert inControl tool facility to hide parameters on keypad is...

Page 255: ...consistent process to promptly monitor for fresh firmware updates and apply the update whenever required The latest firmware can be acquired from the www eaton com drives website There will be separa...

Page 256: ...246 Application notes POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN September 2021 www eaton com Notes...

Page 257: ...247 Application notes POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN September 2021 www eaton com Notes...

Page 258: ...Eaton is a registered trademark All trademarks are property of their respective owners Proof 2 September 22 2021 3 06 PM Eaton Corporation W126N7250 Flint Drive Menomonee Falls WI 53051 USA Eaton Elec...

Reviews: