Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN—September 2021 www.eaton.com
Table 68. Fieldbus (FB) status (Cont.).
P10.2.4
b
FB process data output 4 selection
ID 1559
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
4
Description:
With the fieldbus data output selections, parameter/monitor IDs can be assigned to these registers and then read over the desired
fieldbus network word for process data. Any drive parameter with an ID can be read over these values.
Default values for process data out in fieldbus (build table for below values):
Process data Out1 = Output frequency = ID 1;
Process data Out2 = Motor speed = ID 2;
Process data Out3 = Motor current = ID 3;
Process data Out4 = Motor torque = ID 4;
Process data Out5 = Motor power = ID 5;
Process data Out6 = Motor voltage = ID 6;
Process data Out7 = DC link voltage = ID 7; or
Process data Out8 = Latest fault code = ID 28.
P10.2.5
b
FB process data output 5 selection
ID 1560
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Description:
With the fieldbus data output selections, parameter/monitor IDs can be assigned to these registers and then read over the desired
fieldbus network word for process data. Any drive parameter with an ID can be read over these values.
Default values for process data out in fieldbus (build table for below values):
Process data Out1 = Output frequency = ID 1;
Process data Out2 = Motor speed = ID 2;
Process data Out3 = Motor current = ID 3;
Process data Out4 = Motor torque = ID 4;
Process data Out5 = Motor power = ID 5;
Process data Out6 = Motor voltage = ID 6;
Process data Out7 = DC link voltage = ID 7; or
Process data Out8 = Latest fault code = ID 28.
P10.2.6
b
FB process data output 6 selection
ID 1561
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
6
Description:
With the fieldbus data output selections, parameter/monitor IDs can be assigned to these registers and then read over the desired
fieldbus network word for process data. Any drive parameter with an ID can be read over these values.
Default values for process data out in fieldbus (build table for below values):
Process data Out1 = Output frequency = ID 1;
Process data Out2 = Motor speed = ID 2;
Process data Out3 = Motor current = ID 3;
Process data Out4 = Motor torque = ID 4;
Process data Out5 = Motor power = ID 5;
Process data Out6 = Motor voltage = ID 6;
Process data Out7 = DC link voltage = ID 7; or
Process data Out8 = Latest fault code = ID 28.
P10.2.7
b
FB process data output 7 selection
ID 1562
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
7
Description:
With the fieldbus data output selections, parameter/monitor IDs can be assigned to these registers and then read over the desired
fieldbus network word for process data. Any drive parameter with an ID can be read over these values.
Default values for process data out in fieldbus (build table for below values):
Process data Out1 = Output frequency = ID 1;
Process data Out2 = Motor speed = ID 2;
Process data Out3 = Motor current = ID 3;
Process data Out4 = Motor torque = ID 4;
Process data Out5 = Motor power = ID 5;
Process data Out6 = Motor voltage = ID 6;
Process data Out7 = DC link voltage = ID 7; or
Process data Out8 = Latest fault code = ID 28.