242
Application notes
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE
MN040049EN
—September 2021 www.eaton.com
Fault
code
Fault name/
description
Fault type
Default
configuration Possible cause
Remedy
100
Fieldbus fault
(Fieldbus SMDT
fault)
Fault
Configurable
Smart wire sus fieldbus fault.
Check SmartWire DT card.
101
Option card fault Fault
Configurable
SMDT board hardware fault.
Check SmartWire DT card.
102
External fault
(External fault
from SWD)
Fault
Configurable
External fault from SWD.
Check SmartWire DT card.
103
Drive over
temperature
Warning
Drive degree greater than (DCI_wDriveOverTempThreshold
value - 10 degree) and less than DCI_
wDriveOverTempThreshold value,report drive over temperature
warning.
Check the drive degree.
111
Profibus
firmware
incompatible
Warning
Profibus card firmware is not compatible with MCB firmware. Check the Profibus card firmware
revision.
113
CANOpen
firmware
incompatible
Warning
CANOpen card firmware is not compatible with MCB firmware. Check the CANOpen firmware revision.
114
SWD firmware
incompatible
Warning
SWD card firmware is not compatible with MCB firmware.
Check the SWD card firmware revision.
115
Fieldbus fault
Fault
Configurable
FieldBus EIP idle fault
Check ethernet IP master programming
to verify proper addressing and ensure
idle communication bit is not set.
117
Pump over cycle Warning
During a period, the times which the drive sleeps and wakes up
exceed a user configurable value.
Check the reason that drive is not stable.
Check why the drive sleeps and wakes
up frequently.
118
Broken pipe
Warning
Configurable
PID feedback is less than broken pipe level and the drive
output frequency is more than broke pipe frequency for delay
time.
125
Freq. limit supv.
(Freq. limit)
No action
The output frequency exceeds the range of frequency
supervision limit.
Check the output frequency and check
the setting of frequency supervision
limit.
126
Torque limit
supv.
(Torque limit)
No action
The motor torque exceeds the range of torque supervision
limit.
Check the motor torque and check the
setting of torque supervision limit.
127
Ref. limit supv.
(Ref. limit)
No action
The frequency reference exceeds the range of freq. reference
supervision limit.
Check the frequency reference and
check the setting of frequency reference
supervision limit.
128
Power limit
supv.
(Power limit)
No action
The motor power exceeds the range of power supervision limit. Check the motor power and check the
setting of power supervision limit.
129
Temp. limit supv.
(Temp. limit)
No action
The unit temperature exceeds the range of temperature
supervision limit.
Check the unit temperature and check
the setting of temperature supervision
limit.
130
AI limit supv.
(AI limit)
No action
The AI value exceeds the range of AI supervision limit.
Check the AI value and check the setting
of AI supervision limit.
131
Motor current
supv.
(Motor current
limit)
No action
The motor current exceeds the range of current supervision
limit
Check the motor current and check the
setting of current supervision limit.
132
P
I superv.
No action
The PI1 feedback exceeds the range of PI1 supervision limit.
Check the PI1 feedback and check the
setting of PI1 supervision limit.
133
Fieldbus fault
(Fieldbus web UI
fault)
Fault
Configurable
FieldBus web UI fault.
Check the web connection with RJ45
connector. Verify drive parameters are
set correctly. Check the web UI tool to
know if there is proper request going to
drive or not.