Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN
—September 2021 www.eaton.com
Table 68. Fieldbus (FB) status (Cont.).
P10.2.8
b
FB process data output 8 selection
ID 1563
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
28
Description:
With the fieldbus data output selections, parameter/monitor IDs can be assigned to these registers and then read over the desired
fieldbus network word for process data. Any drive parameter with an ID can be read over these values.
Default values for process data out in fieldbus (build table for below values):
Process data Out1 = Output frequency = ID 1;
Process data Out2 = Motor speed = ID 2;
Process data Out3 = Motor current = ID 3;
Process data Out4 = Motor torque = ID 4;
Process data Out5 = Motor power = ID 5;
Process data Out6 = Motor voltage = ID 6;
Process data Out7 = DC link voltage = ID 7; or
Process data Out8 = Latest fault code = ID 28.
P10.3 - Standard status word.
P10.3.1
b
Standard status word Bit0 function select
ID 2415
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Not used;
1 = Ready;
2 = Run;
3 = Fault;
4 = Fault invert;
5 = Warning;
6 = Reversed;
7 = At speed;
8 = Zero frequency;
9 = Frequency limit supervision;
10 = PI supervision;
11 = Torque limit supervision;
12 = Reference limit supervision;
13 = Power limit supervision;
14 = Temperature limit supervision;
15 = Analog input supervision;
16 = Motor current supervision;
17 = Over heat fault;
18 = Overcurrent regular;
19 = Overvoltage regular;
20 = Undervoltage regular;
21 = 4 mA reference fault/warning;
22 =
External fault/warning;
23 = Moto
r thermal protection;
24 = STO fault output;
25 = Control from I/O;
26 = Remote control;
27 = Un-requested rotation direction;
28 = Fire mode;
29 = Damper control;
30 = Valve control;
31 = Jog speed select;
32 = Fieldbus digital input 1;
33 = Fieldbus digital input 2;
34 = DC charge switch close;
35 = Preheat active;
36 = Cold weather active;
37 = PI Sleep
38 =
2nd stage ramp frequency active;
39 = Prime
pump active;
40 = Master drive state;
41 = Slave drive state; or
43 = Single drive control.
Description:
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard
status word. This also can be viewed in the keypad monitor value M5.3.