Chapter 6 - Pump control application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN
—September 2021 www.eaton.com
Table 40. Parameters (Cont.).
P1.11
b
Local control place
ID 1695
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = keypad;
1 = IO terminal; or
3 = fieldbus.
Description:
Defines the signal location for the start command in local mode. I/O terminals would be from the digital hard-wired inputs or keypad for
Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
P1.12
ab
Local reference
ID 136
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = AI;
1 = drive ref. pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus ref.
Description:
Defines the signal location for the speed reference in local mode.
P1.13
b
Remote control place
ID 135
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = IO terminal;
1 = fieldbus; or
3 = keypad.
Description:
Defines the signal location for the start command in remote mode. I/O terminals would be from the digital hard-wired inputs or keypad
for Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
P1.14
ab
Remote reference
ID 137
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = AI;
1 = drive reference pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus reference.
Description:
Defines the signal location for the speed reference in remote mode.