187
Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
MN040049EN—September 2021 www.eaton.com
Table 60. Drive control (Cont.).
P4.3.6
b
Skip F3 low limit
ID 260
Minimum value:
0.00 HZ
Maximum value:
SkipRange3HighLimit Hz
Default value:
0.00 Hz
Description:
Defines the acceleration/deceleration time when the output frequency is between the selected prohibit frequency range limits. The
ramping speed (selected acceleration/deceleration time 1 or 2) is multiplied with this factor: e.g., value 0.1 makes the acceleration time
10 times shorter than outside the prohibit frequency range limits.
P4.3.7
b
Skip F3 high limit
ID 261
Minimum value:
SkipRange3LowLimit HZ
Maximum value:
400.00 Hz
Default value:
0.00 Hz
Description:
Defines the acceleration/deceleration time when the output frequency is between the selected prohibit frequency range limits. The
ramping speed (selected acceleration/deceleration time 1 or 2) is multiplied with this factor: e.g., value 0.1 makes the acceleration time
10 times shorter than outside the prohibit frequency range limits.
P4.4 - Energy savings calculations.
P4.4.1
b
Currency
ID 2122
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = $;
1 = £;
2 = €;
3 = ¥;
4 = Rs;
5 = R$;
6 = Fr; or
7 = kr.
Description:
Sets the local currency used for energy savings estimation.
P4.4.2
b
Energy cost
ID 2123
Minimum value:
Varies
Maximum value:
Varies
Default value:
0.00 varies
Description:
Sets the local energy cost per kW. Used for energy savings estimation.
P4.4.3
b
Data type
ID 2124
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Cumulative;
1 = Daily average;
2 = Weekly average;
3 = Monthly average; or
4 = Yearly average.
Description:
Selects the format to view energy savings. The drive takes four recordings in an hour and then calculates the average based off this
parameter. The savings estimation is based on comparing the drives energy usage compared to a across the line starter.
P4.4.4
Energy savings reset
ID 2125
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Not reset; or
1 = Reset.
Description:
Resets the energy savings value.
a
Parameter value can only be changed after the drive has stopped.
b
Parameter value will be set to be default when changing macros.