Step 5—Standard Parameter List
18
PowerXL DG1 Series Adjustable Frequency Drives
MN040012EN—March 2014
www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P5.15
2
Temp Limit Supv
0
165
See P5.11
P5.16
2
Temp Limit Supv Val
–10.0
75.0
°C
40.0
166
P5.17
2
Power Limit Supv
0
167
See P5.11
P5.18
2
Power Limit Supv Val
0.0
200.0
%
0.0
168
P5.19
2
AI Supv Select
0
170
0 = AI1
1 = AI2
P5.20
2
AI Limit Supv
0
171
See P5.11
P5.21
2
AI Limit Supv Val
0.00
100.00
%
0.00
172
P5.30
RO1 On Delay
0
320
s
0
2111
P5.31
RO1 Off Delay
0
320
s
0
2112
P5.32
RO2 On Delay
0
320
s
0
2113
P5.33
RO2 Off Delay
0
320
s
0
2114
P5.34
RO3 On Delay
0
320
s
0
2115
P5.35
RO3 Off Delay
0
320
s
0
2116
P5.36
RO3 Reverse
0
1
0
2117
0 = Not Inverted
1 = Inverted
Table 14. Drive Control—P7
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P7.1
2
Remote 2 Control Place
1
138
See P1.11
P7.2
12
Remote 2 Reference
7
139
See P1.12
P7.3
2
Keypad Reference
Par. P1.1
Par. P1.2
Hz
0.00
141
P7.4
2
Keypad Direction
0
116
0 = Forward
1 = Reverse
P7.5
2
Keypad Stop
1
114
0 = Enabled-Keypad Operation
1 = Always Enabled
P7.6
2
Jog Reference
Par. P1.1
Par. P1.2
Hz
0.00
117
P7.9
2
Start Mode
0
252
0 = Ramp
1 = Flying Start
P7.10
2
Stop Mode
1
253
0 = Coasting
1 = Ramp
P7.11
2
Ramp 1 Shape
0.0
10.0
s
0.0
247
P7.12
2
Ramp 2 Shape
0.0
10.0
s
0.0
248
P7.13
2
Accel Time 2
0.1
3000.0
s
10.0
249
P7.14
2
Decel Time 2
0.1
3000.0
s
10.0
250
P7.15
2
Skip F1 Low Limit
0.00
Par. P7.16
Hz
0.00
256
P7.16
2
Skip F1 High Limit
Par. P7.15
400.00
Hz
0.00
257
P7.17
2
Skip F2 Low Limit
0.00
Par. P7.18
Hz
0.00
258
P7.18
2
Skip F2 High Limit
Par. P7.17
400.00
Hz
0.00
259
P7.19
2
Skip F3 Low Limit
0.00
Par. P7.20
Hz
0.00
260
P7.20
2
Skip F3 High Limit
Par. P7.19
400.00
Hz
0.00
261
P7.21
2
Prohibit Accel/Decel Ramp 0.1
10.0
1.0
264
Table 13. Digital Output—P5, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
Courtesy
of
CMA/Flodyne/Hydradyne
▪
Motion
Control
▪
Hydraulic
▪
Pneumatic
▪
Electrical
▪
Mechanical
▪
(800)
426-5480
▪
www.cmafh.com