Step 5—Standard Parameter List
PowerXL DG1 Series Adjustable Frequency Drives
MN040012EN—March 2014
www.eaton.com
13
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 8. Operate Mode—O
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
O1
Output Frequency
Hz
0.00
1
O2
Freq Reference
Hz
0.00
24
O3
Motor Speed
rpm
0
2
O4
Motor Current
A
0.0
3
O5
Motor Torque
%
0.0
4
O6
Motor Power
%
0.0
5
O7
Motor Voltage
V
0.0
6
O8
DC-link Voltage
V
0
7
O9
Unit Temperature
°C
0.0
8
O10
Motor Temperature
%
0.0
9
R12
2
Keypad Reference
Par. P1.1
Par. P1.2
Hz
0.00
141
Table 9. Basic Parameters—P1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P1.1
2
Min Frequency
0.00
Par. P1.2
Hz
0.00
101
P1.2
2
Max Frequency
Par. P1.1
400.00
Hz
Max Freq
102
P1.3
2
Accel Time 1
0.1
3000.0
s
3.0
103
P1.4
2
Decel Time 1
0.1
3000.0
s
3.0
104
P1.5
1
Motor Nom Current
Drive Nom
CT*1/10
Drive Nom
CT*2
A
Drive Nom CT
486
P1.6
1
Motor Nom Speed
300
20000
rpm
Motor Nom Speed
489
P1.7
1
Motor PF
0.30
1.00
0.85
490
P1.8
1
Motor Nom Voltage
180
690
V
Motor Nom Voltage 487
P1.9
1
Motor Nom Frequency
8.00
400.00
Hz
Motor Nom Freq
488
P1.10
2
Local/Remote Select
0
140
0 = Hold Last
1 = Local Control
2 = Remote Control
P1.11
2
Remote1 Control Place
0
135
0 = I/O Terminal
1 = Fieldbus
P1.12
Local Control Place
0
1695
0 = Keypad
1 = I/O Terminal