Step 4—Startup Wizard
8
PowerXL DG1 Series Adjustable Frequency Drives
MN040012EN—March 2014
www.eaton.com
Step 4—Startup Wizard
Startup Wizard
In the
Startup Wizard
, you will be prompted for essential
information needed by the drive so that it can start
controlling your process. In the Wizard, you will need
the following keypad buttons:
Up/Down buttons.
Use these to change value.
OK button.
Confirm selection with this button, and enter into
next question.
Back/Reset button.
If this button was pressed at the first question,
the Startup Wizard will be cancelled.
Once you have connected power to your Eaton PowerXL
DG1 frequency converter, and the Startup Wizard is enabled,
follow these instructions to easily set up your drive.
Table 5. Startup Wizard Instructions
Now the Startup Wizard is done. It won’t show again when
next power up. If you want to reset it, please set the Startup
Wizard (P21.1.9) or select it from the main menu screen to
enable and cycle the power to the drive.
Item
Description
1
Startup Wizard
Press OK?
2
Language
0 = English
1 =
ѝ᮷
2 = Deutsch
3
Real Time Clock
yy.mm.dd
hh:mm:ss
4
Daylight Saving
0 = Off
1 = EU
2 = US
5
Application
0 = Standard
1 = Multi-Pump
2 = Multi-PID
3 = Multi-Purpose
6
Min Frequency
Min: 0.00Hz
Max: Max Frequency
7
Max Frequency
Min: Min Frequency
Max: 400.00Hz
8
Motor Nom Current
Min: 0.1A
Max: 500.0A
9
Current Limit
Min: Ih*1/10
Max: Ih*2
10
Motor Nom Speed
Min: Ih*1/10
Max: Ih*2
11
Motor PF
Min: 0.30
Max: 1.0
12
Motor Nom Volt
Min: 180V
Max: 690V
13
Motor Nom Freq
Min: 30.00 Hz
Max: 400.00 Hz
14
Motor Nom Power
Min: 0.1 kW
Max:5000.0 kW
15
Application Mini-Wizard
Press OK?