Step 5—Standard Parameter List
20
PowerXL DG1 Series Adjustable Frequency Drives
MN040012EN—March 2014
www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 16. Protections—P9
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P9.1
12
4 mA Input Fault
0
306
0 = No Action
1 = Warning
2 = Warning: Previous Freq
3 = Warning: Preset Freq
4 = Fault
5 = Fault, Coast
P9.2
12
4 mA Fault Frequency
0.00
Par. P1.2
Hz
0.00
331
P9.3
12
External Fault
2
307
See P9.11
P9.4
12
Input Phase Fault
2
332
See P9.11
P9.5
12
Uvolt Fault Response
2
330
See P9.11
P9.6
12
Output Phase Fault
2
308
See P9.11
P9.7
12
Ground Fault
2
309
See P9.11
P9.8
12
Motor Thermal Protection
2
310
See P9.11
P9.9
2
Motor Thermal F0 Current
0.0
150.0
%
40.0
311
P9.10
2
Motor Thermal Time
1
200
min
12
312
P9.11
12
Stall Protection
0
313
0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
P9.12
2
Stall Current Limit
0.1
Active Motor
Nom
I
*2
A
Active Motor Nom
I
*13/10
314
P9.13
2
Stall Time Limit
1.0
120.0
s
15.0
315
P9.14
2
Stall Frequency Limit
1.00
Par. P1.2
Hz
25.00
316
P9.15
12
Underload Protection
0
317
See P9.11
P9.16
2
Underload Fnom Torque
10.0
150.0
%
50.0
318
P9.17
2
Underload F0 Torque
5.0
150.0
%
10.0
319
P9.18
2
Underload Time Limit
2.00
600.00
s
20.00
320
P9.19
12
Thermistor Fault Response
2
333
See P9.11
P9.20
2
Line Start Lockout
2
750
0 = Disabled, No Change
1 = Enable, No Change
2 = Disabled, Changed
3 = Enable, Changed
P9.21
12
Fieldbus Fault Response
2
334
See P9.11
P9.22
12
OPTCard Fault Response
2
335
See P9.11
P9.23
12
Unit Under Temp Prot
2
1564
See P9.11
P9.24
2
Wait Time
0.10
10.00
s
0.50
321
P9.25
2
Trail Time
0.00
60.00
s
30.00
322
P9.26
2
Start Function
0
323
0 = Ramp
1 = Flying Start
2 = Start
P9.27
2
Undervoltage Attempts
0
10
1
324
P9.28
2
Overvoltage Attempts
0
10
1
325
P9.29
2
Overcurrent Attempts
0
3
1
326
P9.30
2
4 mA Fault Attempts
0
10
1
327
P9.31
2
Motor Temp Fault Attempts 0
10
1
329
Courtesy
of
CMA/Flodyne/Hydradyne
▪
Motion
Control
▪
Hydraulic
▪
Pneumatic
▪
Electrical
▪
Mechanical
▪
(800)
426-5480
▪
www.cmafh.com