Step 5—Standard Parameter List
22
PowerXL DG1 Series Adjustable Frequency Drives
MN040012EN—March 2014
www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 19. FB Data Output Sel—P20.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P20.1.1
2
FB Data Output 1 Sel
1
1556
P20.1.2
2
FB Data Output 2 Sel
2
1557
P20.1.3
2
FB Data Output 3 Sel
3
1558
P20.1.4
2
FB Data Output 4 Sel
4
1559
P20.1.5
2
FB Data Output 5 Sel
5
1560
P20.1.6
2
FB Data Output 6 Sel
6
1561
P20.1.7
2
FB Data Output 7 Sel
7
1562
P20.1.8
2
FB Data Output 8 Sel
359
1563
Table 20. Modbus RTU/BACnet MS/TP—P20.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P20.2.1
RS485 Comm Set
0
586
0 = Modbus RTU
1 = BACnet MS/TP
P20.2.2
Slave Address
1
247
18
587
P20.2.3
Baud Rate
2
584
0 = 9600
1 = 19200
2 = 38400
3 = 76800
4 = 115200
P20.2.4
Parity Type
2
585
0 = None
1 = Odd
2 = Even
P20.2.5
Protocol Status
0
588
0 = Initial
1 = Stopped
2 = Operational
3 = Faulted
P20.2.6
Slave Busy
0
589
0 = Not Busy
1 = Busy
P20.2.7
Parity Error
0
590
P20.2.8
Slave Fault
0
591
P20.2.9
Last Fault Response
0
592
P20.2.10
Comm Timeout Modbus RTU
ms
2000
593
P20.2.11
BACnet Baud Rate
2
594
0 = 9600
1 = 19200
2 = 38400
3 = 76800
4 = 115200
P20.2.12
MAC Address
0
127
1
595
P20.2.13
Instance Number
0
4194302
0
596
P20.2.14
Comm Timeout BACnet
ms
6000
598
P20.2.15
Protocol Status
0
599
0 = Stopped
1 = Operational
2 = Faulted
P20.2.16
Fault Code
0
600
0 = None
1 = Sole Master
2 = Duplicate MAC ID
3 = Baud rate fault