Tap Off Modules

Step 1.

In accordance with isolation procedures and risk 

assessments to be carried out by the installer, ensure 

complete isolation of the electrical busbar by proving dead.

Step 2.

Following removal of the tap off unit from its packaging, 

check the device is not damaged and tap off contacts are 

visually in line.

Step 3.

 

Open door using key provided and release both clamping 

mechanisms by using a 6mm t-bar in an anticlockwise 

direction.

Tap off box

MCCB

Lock

Secure rear fi xing brackets

Step 4.

Offer the tap off box up to the shutter housing and visually 

line up the earth contact bracket and actuator to ensure 

correct location of the tap off contacts. 

The box cannot be inserted upside down as the design of 

the actuator mechanism prevents this. 

Insert the tap off box until base of tap off box fi nishes fl ush 

with busbar assembly.

Use the 6mm t-bar to clamp the tap off box to the busbar 

assembly by rotating the clamping mechanism in a 

clockwise direction. 

Step 5.

Install the rear fi xing brackets as illustrated below.

Step 7.

Megger test installation prior to re-energisation of busbar.

Step 8.

Before turning the Breaker “ON”, ensure the neutral link is 

connected and tightened.

Handle

Summary of Contents for Power Xpert XP2

Page 1: ...Power Xpert XP2 Power Xpert XP2 Installation Manual Installation Manual www eaton eu busbars OHSAS 18001 2007 OHS 533652 ISO 9001 2008 FM 12680 ISO 14001 2004 No EMS 566536...

Page 2: ...ot exceed the safe working load of the lifting apparatus Ensure that equipment is used as per manufacturer s guidelines Storage The Busbar will be delivered to the customer neatly stacked on a wooden...

Page 3: ...ific area Eaton recommend that the fixing brackets must be mounted no more than 500mm from the centre of the joints For vertical riser installation of sections greater than 2 metres it may be easier t...

Page 4: ...t is the responsibility of the support system supplier to ensure their system can safely support the weight of our product Please note Eaton fixing bracket s must be used Drilling or cutting the busba...

Page 5: ...to Unistrut with M10 Hex Bolt and Lock Nut tighten the bolts to 45Nm 5Nm Step 4 Attach Spring Hanger Brackets to Busbar using fixing brackets Step 5 Tighten the joint pack to 65Nm 5Nm once the spring...

Page 6: ...ntact surfaces are free from contaminates unblemished not damaged correctly aligned Step 4 a Position Busbar B as shown in the image Ensure that the Earth side plate is not overlapping the Expansion R...

Page 7: ...on Step 1 Mount Busbar to frame Step 2 Install the Joint Pack Elbow to Busbar never force the joint or strike it with any object as this may damage the Joint or Busbar section The joint should be inse...

Page 8: ...EATON wb xp2 en 8...

Page 9: ...e required to install the Cable End Box following the instructions shown Unistrut rail Access cover Gland plate 2 3 M10 Channel Nut M10 Bolt 1 Unistrut rail 2 Access cover 3 Gland plate Tap Off Cover...

Page 10: ...ng brackets Step 4 Offer the tap off box up to the shutter housing and visually line up the earth contact bracket and actuator to ensure correct location of the tap off contacts The box cannot be inse...

Page 11: ...sitive ON OFF operation Examine protective device for sign of short circuit operation If a short circuit has occurred on the equipment connected to the tap off module check operation of device and the...

Page 12: ...aton eu Eaton Electric Ltd 270 Bath Road Slough Berkshire SL1 4DX Tel 01753 608 700 Email systemquotes eaton com www eaton com To contact an Eaton salesperson or local distributor agent please visit w...

Reviews: